Electrical Junior Engineer: Special Machines, Alternators in Parallel, and the Utilisation of Electrical Energy
2. The alternator: EMF, armature reaction and parallel operation
The speed of a synchronous machine is fixed by the supply frequency and the number of poles: N = 120 f ÷ P rpm, so a 4-pole machine at 50 Hz runs at 1,500 rpm. The EMF induced per phase is E = 4.44 f Φ T (times the winding factors, taken as 1 here): with f = 50 Hz, a flux of 0.05 Wb per pole and 200 turns per phase, E = 4.44 × 50 × 0.05 × 200 = 2,220 V per phase, and in a star connection the line voltage is √3 times this, about 3,845 V. Voltage regulation is how much the terminal voltage rises when the load is thrown off: (no-load voltage − full-load voltage) ÷ full-load voltage × 100, so 2,400 V at no load and 2,200 V at full load is 9.09 percent.
| Load power factor | Armature reaction on the main field | Effect on terminal voltage |
|---|---|---|
| Unity | Cross-magnetising (distorts the field) | Small fall |
| Lagging (inductive) | Demagnetising (weakens the field) | Large fall |
| Leading (capacitive) | Magnetising (strengthens the field) | Rise (Ferranti-like) |
To connect an alternator to a live bus (synchronisation) four conditions must be met: equal terminal voltage, equal frequency, the same phase sequence and zero phase-angle difference at the instant of closing. A synchroscope, or the three-lamp method, shows this. After paralleling, the governor setting decides how real power (kW) is shared, and the excitation decides how reactive power (kVAr) is shared; raising the prime-mover input on one machine makes it take more kW without changing the bus frequency much, which is controlled by the sum of all machines. Closing out of step produces a heavy circulating current and a mechanical shock.
The speed of a synchronous machine is fixed by the supply frequency and the number of poles: N = 120 f ÷ P rpm, so a 4-pole machine at 50 Hz runs at 1,500 rpm. The EMF induced per phase is…
3. Illumination
Luminous intensity is measured in candela, luminous flux in lumen and illuminance (flux per unit area) in lux, where 1 lux = 1 lumen per square metre. For a point source the inverse square law gives E = I ÷ d² on a surface facing the source: 1,000 cd at 4 m gives 62.5 lux. When the surface is tilted, the cosine law gives E = I cos θ ÷ d², so 1,000 cd hanging 3 m above a point 5 m away along the line of sight (cos θ = 3/5 = 0.6) gives 1,000 × 0.6 ÷ 25 = 24 lux. A source of intensity I in every direction emits 4π I lumens; 100 cd gives about 1,257 lm.
Room lighting is designed by the lumen method: N = E × A ÷ (F × UF × MF), where E is the required lux, A the floor area, F the lumens per lamp, UF the utilisation factor (the share of lamp lumens reaching the work plane) and MF the maintenance factor (allowing for dirt and ageing). For a 10 m × 6 m workshop needing 300 lux, with 3,000 lm lamps, UF = 0.5 and MF = 0.8, N = 300 × 60 ÷ (3,000 × 0.5 × 0.8) = 15 lamps. Efficacy is lumens per watt; LED lamps give several times the efficacy of filament lamps, which is why replacement saves energy.
Luminous intensity is measured in candela, luminous flux in lumen and illuminance (flux per unit area) in lux, where 1 lux = 1 lumen per square metre. For a point source the inverse square…
4. Electric heating, welding and electroplating
Resistance heating follows Joule's law, H = I²Rt, and 1 kWh = 3.6 MJ. To heat 50 kg of water from 20 °C to 60 °C needs 50 × 4.186 × 40 = 8,372 kJ; on a 2 kW heater of 80 percent efficiency this takes 8,372 ÷ (2 × 0.8) = 5,232 s, about 87 minutes. Other methods match the material: arc furnaces for melting steel, induction heating (eddy currents in a conducting charge, with higher frequency for a thinner heated layer) for hardening and melting, and dielectric heating (a high-frequency field acting on an insulator such as wood or plastic) for glueing and drying. Arc welding uses a transformer or rectifier with a drooping characteristic so the current stays near constant as the arc length varies; resistance welding (spot, seam, butt) uses a very large current for a short time through the joint.
Electroplating obeys Faraday's first law: the mass deposited is m = Z I t, where Z is the electrochemical equivalent of the metal. For copper Z is about 0.329 mg per coulomb (0.000329 g/C), so 10 A for one hour deposits 0.000329 × 10 × 3,600 ≈ 11.8 g. The article to be plated is the cathode, the plating metal is the anode, and the electrolyte is a salt of the plating metal. Doubling the current, or the time, doubles the deposit; it does not change the thickness pattern by itself, which also depends on current density.
Resistance heating follows Joule's law, H = I²Rt, and 1 kWh = 3.6 MJ. To heat 50 kg of water from 20 °C to 60 °C needs 50 × 4.186 × 40 = 8,372 kJ; on a 2 kW heater of 80 percent efficiency…
5. Electric traction and drives
Indian Railways' main-line standard is single-phase 25 kV, 50 Hz AC from overhead wires. A traction motor must give a high starting torque and be insensitive to supply changes, which is why the series characteristic, with torque falling as speed rises, historically suited it; modern locomotives use converters and three-phase induction drives. Tractive effort at steady speed equals the train resistance. For a 500 tonne train with 40 N per tonne resistance on level track the tractive effort is 500 × 40 = 20 kN, and at 10 m/s (36 km/h) the wheel power is 20,000 × 10 = 200 kW, or 250 kW input at 80 percent efficiency.
Specific energy consumption is the energy per tonne-kilometre. Over 10 km the wheel energy is 20,000 × 10,000 J = 200 MJ = 55.56 kWh; at 80 percent efficiency the input is 69.4 kWh, and per tonne-km that is 69.4 ÷ (500 × 10) = 0.0139 kWh, about 13.9 Wh per tonne-km. A trapezoidal speed-time curve (acceleration, free run, coasting, braking) is the standard model; coasting saves energy. Braking is by friction brakes, dynamic braking (the motor works as a generator into resistors) or regenerative braking (the energy goes back to the supply). Speed of an induction motor drive is controlled by changing frequency: a 4-pole motor at 40 Hz has a synchronous speed of 120 × 40 ÷ 4 = 1,200 rpm.
Indian Railways' main-line standard is single-phase 25 kV, 50 Hz AC from overhead wires. A traction motor must give a high starting torque and be insensitive to supply changes, which is why…
Second Pass: EMF per Phase, Voltage Regulation, Oblique Illumination and Heater Resistance
The EMF per phase of an alternator is E = 4.44 f Φ T (taking the winding factor as one). Voltage regulation is (no-load − full-load voltage)/full-load voltage. For a point source, illuminance at a point is I cos θ/d², with d the distance and θ the angle from the vertical. A resistance heater has R = V²/P, and the mass deposited in electroplating depends only on the total charge.
| Item | Working | Answer |
|---|---|---|
| f = 50, Φ = 0.02 Wb, T = 100 | 4.44 × 50 × 0.02 × 100 | 444 V |
| 440 V no load, 400 V full load | (440 − 400)/400 | 10% |
| 1,000 cd, 4 m high, 3 m sideways | 1,000/25 × 0.8 | 32 lux |
| 2 kW heater on 200 V | 200²/2,000 | 20 Ω |
The EMF per phase of an alternator is E = 4.44 f Φ T (taking the winding factor as one). Voltage regulation is (no-load − full-load voltage)/full-load voltage. For a point source…
Key takeaways
- A single winding gives a pulsating field with no starting torque; split-phase, capacitor-start and shaded-pole motors all create a second flux displaced in space and time.
- Synchronous speed is 120 f ÷ P; the alternator EMF per phase is 4.44 f Φ T; lagging loads demagnetise and leading loads magnetise through armature reaction.
- Paralleling needs equal voltage, frequency, phase sequence and phase angle; the governor shares kW and the excitation shares kVAr.
- The lumen method is N = E A ÷ (F × UF × MF); the inverse-square and cosine laws give illuminance from a point source.
- 1 kWh is 3.6 MJ; electroplating deposit is m = Z I t with the article as cathode; arc welding wants a drooping characteristic.
- Steady tractive effort equals train resistance; specific energy is quoted in Wh per tonne-km, and regenerative braking returns energy to the line.
Practice questions (25)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
Why is a single-phase induction motor with only one winding not self-starting?
Show answer
Answer: B — Its field only pulsates, so the two opposite rotating fields give zero net starting torque
A single winding produces a pulsating flux equal to two equal rotating fluxes in opposite directions; at standstill their torques cancel. The other options describe features that a working motor does have.Which single-phase motor works on both AC and DC supplies?
Show answer
Answer: C — Universal motor
A series-wound motor with laminated poles gives torque in the same direction whichever way the current flows, so it runs on both. The other three are induction motors and need AC.A stepper motor has a step angle of 1.8°. At 200 pulses per second it rotates at:
Show answer
Answer: D — 60 rpm
It makes 360 ÷ 1.8 = 200 steps per revolution, so 200 pulses a second is one revolution a second, 60 rpm. Choosing 200 rpm confuses pulses per second with revolutions per minute.
Show the other 22 questions
The synchronous speed of a 6-pole alternator at 50 Hz is:
Show answer
Answer: A — 1,000 rpm
N = 120 f ÷ P = 120 × 50 ÷ 6 = 1,000 rpm. The 1,500 rpm figure belongs to a 4-pole machine.For an alternator supplying a lagging power-factor load, armature reaction is mainly:
Show answer
Answer: B — Demagnetising
A lagging armature current produces an MMF that opposes the field, weakening it and lowering terminal voltage. A leading load does the opposite and unity power factor is cross-magnetising.Which of these is NOT a condition for paralleling an alternator with the bus?
Show answer
Answer: C — Equal power rating
The ratings of machines may differ; they then share load in proportion to their governor settings. Voltage, frequency, sequence and phase angle must match.The unit of illuminance is:
Show answer
Answer: D — Lux
Lux is lumen per square metre. Candela measures intensity, lumen measures flux and lumen per watt is efficacy.A point source of 1,000 cd gives, on a surface 4 m directly below it, an illuminance of:
Show answer
Answer: A — 62.5 lux
E = I ÷ d² = 1,000 ÷ 16 = 62.5 lux. Dividing by d instead of d² gives 250.A hall of 60 m² needs 300 lux. Lamps give 3,000 lm each, UF = 0.5, MF = 0.8. How many lamps?
Show answer
Answer: B — 15
N = 300 × 60 ÷ (3,000 × 0.5 × 0.8) = 18,000 ÷ 1,200 = 15. Forgetting UF and MF gives 6.In electroplating, the article to be plated is made the:
Show answer
Answer: C — Cathode
Metal ions are reduced at the cathode and deposit there. The plating metal is the anode and dissolves to replace them.A steady 500 tonne train with 40 N per tonne resistance runs on level track at 10 m/s. The tractive power at the wheels is:
Show answer
Answer: D — 200 kW
Tractive effort = 500 × 40 = 20,000 N; power = force × speed = 20,000 × 10 = 200,000 W = 200 kW.An alternator winding has 100 turns per phase and the flux per pole is 0.02 Wb. At 50 Hz, taking the winding factor as unity, the EMF per phase is:
Show answer
Answer: A — 444 V
E = 4.44 f Φ T = 4.44 × 50 × 0.02 × 100 = 444 V. Using 2.22 (the half factor) would give 222 V.An alternator gives 440 V at no load and 400 V at full load at the same excitation. Its voltage regulation is:
Show answer
Answer: A — 10%
Regulation = (440 − 400)/400 = 10%, with the full-load voltage as the base. The 9.1% uses the no-load voltage as the base.A lamp of 1,000 candela is suspended 4 m above a table. The illuminance at a point on the table 3 m horizontally from the point directly below the lamp is:
Show answer
Answer: A — 32 lux
The slant distance is 5 m and cos θ = 4/5, so E = 1,000 × 0.8/25 = 32 lux. The 62.5 lux is the value directly below (1,000/16).A heating element rated 2 kW at 200 V has a resistance of:
Show answer
Answer: A — 20 Ω
R = V²/P = 40,000/2,000 = 20 Ω, and the current is 10 A. The 10 Ω confuses resistance with current.In electroplating, the current is doubled and the time is halved. The mass of metal deposited, compared with the original, is:
Show answer
Answer: A — The same
By Faraday's first law the mass is proportional to the charge, Q = It, which is unchanged when I doubles and t halves.An electric locomotive exerts a steady tractive effort of 20 kN at a speed of 15 m/s. The power developed at the wheels is:
Show answer
Answer: A — 300 kW
Power = force × speed = 20,000 × 15 = 3,00,000 W = 300 kW. The 3,000 kW is a factor of ten out.The synchronous speed of a 4-pole alternator on a 50 Hz system is:
Show answer
Answer: A — 1,500 rpm
Ns = 120 f/P = 120 × 50/4 = 1,500 rpm; a 2-pole machine gives 3,000 rpm.An electric locomotive exerts a steady tractive effort of 30 kN at a speed of 20 m/s. The power developed is:
Show answer
Answer: B — 600 kW
Power = force × speed = 30,000 × 20 = 6,00,000 W = 600 kW. Adding the numbers (50) or dividing (1.5) are the tempting slips.A stepper motor with a step angle of 1.8° needs how many pulses for one full revolution?
Show answer
Answer: D — 200
360° ÷ 1.8° = 200 steps per revolution. Check: 200 × 1.8 = 360. The figure 180 is the tempting half-way guess.According to the inverse square law, if the distance of a point source from a surface is doubled, the illuminance on the surface becomes:
Show answer
Answer: D — One-fourth
Illuminance ∝ 1/d², so doubling d gives 1/4. One-half is the tempting answer from forgetting the square.A 3 kW electric heater runs for 2 hours with 80% of its energy going to the water. The heat delivered to the water is:
Show answer
Answer: A — 17.28 MJ
Heat = 3 × 2 × 0.8 = 4.8 kWh, and 4.8 × 3.6 MJ = 17.28 MJ. The 21.6 MJ is the full 6 kWh without efficiency, and 4.8 is in kWh, not MJ.Consider the following statements about electric braking:
1. Regenerative braking returns the braking energy to the supply.
2. Rheostatic braking dissipates the energy as heat in resistors.
Which of the statements given above is/are correct?Show answer
Answer: A — Both 1 and 2
Regeneration feeds energy back to the line and rheostatic braking wastes it as heat. Swapping the two descriptions is the tempting error.A synchronous motor running over-excited draws a current that is:
Show answer
Answer: A — Leading, so it acts like a capacitor and can improve the power factor
Over-excitation makes the motor draw leading current, which is why a synchronous condenser corrects lagging loads. Lagging current belongs to under-excitation, the tempting reversal.For an alternator feeding a leading power-factor load, the full-load terminal voltage compared with the no-load voltage at the same excitation can be:
Show answer
Answer: D — Higher, giving a negative regulation
A leading load produces a magnetising armature reaction that raises the voltage, so regulation can be negative. Always lower is the tempting answer drawn from lagging loads.