Electrical Engineering Basics: Circuits, AC, Transformers, Machines and Supply
2. Alternating current, reactance, impedance and power factor
For a sine wave, RMS = peak ÷ √2 (0.707 × peak) and average (half-cycle) = 0.637 × peak; the form factor RMS ÷ average is 1.11. An inductor offers inductive reactance XL = 2πfL and a capacitor capacitive reactance XC = 1 ÷ (2πfC); at 50 Hz, 0.1 H gives XL = 31.4 Ω and 100 µF gives XC = 31.8 Ω. In a series R-L circuit the impedance is Z = √(R² + X²): with R = 30 Ω and XL = 40 Ω, Z = 50 Ω; on 230 V the current is 230 ÷ 50 = 4.6 A, lagging the voltage by an angle whose cosine, the power factor, is R ÷ Z = 0.6. Real power is P = VI cos φ = 230 × 4.6 × 0.6 = 634.8 W; apparent power is VI in volt-amperes (VA), reactive power VI sin φ in VAR. In a pure inductor the current lags the voltage by 90°; in a pure capacitor it leads by 90° ("ELI the ICE man").
Series resonance occurs when XL = XC, so the impedance is the minimum (just R) and the current maximum, at f₀ = 1 ÷ (2π√LC); for L = 10 mH and C = 10 µF, f₀ = 503 Hz. A low power factor means more current for the same real power, so larger cables and more losses, which is why supply authorities require power-factor correction by parallel capacitors. In a three-phase system with line voltage VL and line current IL, the real power is √3 × VL × IL × cos φ; at 415 V, 10 A and power factor 0.8 it is √3 × 415 × 10 × 0.8 = about 5,750 W. In a star connection VL = √3 × Vph and IL = Iph; in a delta VL = Vph and IL = √3 × Iph.
For a sine wave, RMS = peak ÷ √2 (0.707 × peak) and average (half-cycle) = 0.637 × peak; the form factor RMS ÷ average is 1.11. An inductor offers inductive reactance XL = 2πfL and a…
3. The transformer and the electrical machines
A transformer transfers AC power between circuits by mutual induction, at the same frequency, with no moving parts. Its turns ratio N₁ ÷ N₂ = V₁ ÷ V₂ = I₂ ÷ I₁ (ideal), so a 2,200/220 V unit with 1,000 primary turns has 100 secondary turns. The EMF equation is E = 4.44 f Φm N: at 230 V, 50 Hz and 500 turns, the peak flux is 230 ÷ (4.44 × 50 × 500) = 2.07 mWb. Losses are iron (core) losses (hysteresis and eddy-current, constant with load, reduced by silicon-steel laminations) and copper losses (I²R, varying with load). If the output is 4,000 W with iron loss 100 W and copper loss 150 W, the efficiency is 4,000 ÷ (4,000 + 100 + 150) = 94.1%; efficiency is greatest when the copper loss equals the iron loss. A transformer cannot work on DC, a step-up raises voltage and lowers current, and an autotransformer has one winding shared by primary and secondary.
| Machine | Principle and key relations |
|---|---|
| DC motor | Current-carrying armature in a field feels a force (Fleming's left-hand rule); back EMF Eb = V − IaRa, so at 220 V, Ia = 20 A and Ra = 0.5 Ω, Eb = 210 V; at start Eb = 0 and the current would be 220 ÷ 0.5 = 440 A, hence a starter; series motor has high starting torque (traction), shunt motor nearly constant speed |
| DC generator | Fleming's right-hand rule; EMF induced by flux cutting; commutator converts the armature AC to DC |
| Three-phase induction motor | Synchronous speed Ns = 120f ÷ P: 4 poles at 50 Hz give 1,500 rpm; running speed is lower, with slip s = (Ns − N) ÷ Ns, so 1,440 rpm is a slip of 4% and rotor frequency s × f = 2 Hz; self-starting, rugged, the most used industrial motor |
| Alternator (synchronous generator) | Produces AC at f = PN ÷ 120; the generator of power stations; a synchronous motor runs at exactly Ns and can correct power factor |

A transformer transfers AC power between circuits by mutual induction, at the same frequency, with no moving parts. Its turns ratio N₁ ÷ N₂ = V₁ ÷ V₂ = I₂ ÷ I₁ (ideal), so a 2,200/220 V…
4. Power supply, protection, earthing and measurement
Electric power moves through generation (thermal, hydro, nuclear, renewable), transmission at high voltage (raised by step-up transformers to cut the I²R loss), sub-transmission and distribution at low voltage to consumers, in India at 50 Hz. Protection devices: a fuse melts on over-current; a miniature circuit breaker (MCB) trips on over-current and short circuit and can be reset; an earth-leakage circuit breaker (ELCB or RCCB) trips on leakage to earth, protecting people; a relay senses a fault and trips a larger circuit breaker. Earthing connects the metal frame of equipment to the ground so that a fault current flows to earth and trips the protection, rather than leaving the casing live. Never work on a circuit without isolating it, locking it off and proving it dead.
| Instrument | Measures and how connected |
|---|---|
| Ammeter | Current; connected in series; low resistance |
| Voltmeter | Voltage; connected in parallel; high resistance |
| Wattmeter | Real power; current coil in series, pressure (voltage) coil in parallel |
| Energy meter | Energy in kWh; the induction type has a rotating disc whose turns are proportional to energy |
| Megger | Insulation resistance of cables and windings (high-voltage hand-cranked or electronic tester) |
Electric power moves through generation (thermal, hydro, nuclear, renewable), transmission at high voltage (raised by step-up transformers to cut the I²R loss), sub-transmission and…
Worked Drills: Impedance, Power, Star Voltage, Machine Speed and the Bridge
Six relations solve most Junior Engineer electrical numericals: Z = √(R² + (XL − XC)²); P = V I cos φ for a single-phase load; line voltage = √3 × phase voltage in a star connection; synchronous speed Ns = 120 f / P; transformer turns ratio V₁/V₂ = N₁/N₂ = I₂/I₁ (ideal); and, for a balanced bridge, P/Q = R/S. Always write the unit beside each number.
| Question | Working | Answer |
|---|---|---|
| R = 8 Ω, XL = 12 Ω, XC = 6 Ω, 100 V | Z = √(64 + 36) = 10 Ω; I = 100/10 | 10 A |
| 230 V, 5 A, power factor 0.8 | 230 × 5 × 0.8 | 920 W |
| 6-pole machine at 50 Hz | 120 × 50/6 | 1000 rpm |
| Star, phase voltage 230 V | 1.732 × 230 | ≈ 398 V |
Six relations solve most Junior Engineer electrical numericals: Z = √(R² + (XL − XC)²); P = V I cos φ for a single-phase load; line voltage = √3 × phase voltage in a star connection…
Key takeaways
- Ohm V = IR, KCL (currents at a node sum to zero), KVL (voltages round a loop sum to zero); series resistances add, parallel reciprocals add; 1 kWh is the commercial unit of energy.
- Thevenin and Norton equivalents, superposition for linear networks, and maximum power transfer when load resistance equals source resistance.
- XL = 2πfL, XC = 1 ÷ 2πfC, Z = √(R² + X²), power factor = R ÷ Z, P = VI cos φ; resonance at 1 ÷ 2π√LC; three-phase power √3 VL IL cos φ.
- Transformer: V₁ ÷ V₂ = N₁ ÷ N₂, E = 4.44 f Φm N, iron loss constant, copper loss varies with load, maximum efficiency when they are equal; it does not work on DC.
- DC motor back EMF Eb = V − IaRa and a starter limits the starting current; induction motor Ns = 120f ÷ P with slip s = (Ns − N) ÷ Ns.
- Protection: fuse, MCB, ELCB or RCCB, relay and breaker; earthing sends fault current to ground; ammeter in series with low resistance, voltmeter in parallel with high resistance.
Practice questions (25)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
A 6 Ω and a 3 Ω resistor are connected in parallel. Their equivalent resistance is:
Show answer
Answer: C — 2 Ω
For parallel resistors 1/R = 1/6 + 1/3 = 1/2, so R = 2 Ω. The 9 Ω figure is the series sum, and the equivalent of parallel resistors is always less than the smallest.An ammeter is connected in a circuit:
Show answer
Answer: A — In series, with low resistance
An ammeter carries the whole circuit current, so it is placed in series and made low in resistance so that it does not disturb the current. A voltmeter is the parallel, high-resistance one.A transformer cannot be used to change the voltage of:
Show answer
Answer: D — Steady DC
A transformer works by mutual induction, which needs a changing flux, so steady DC produces no induced voltage in the secondary.
Show the other 22 questions
In a series circuit, R = 30 Ω and the inductive reactance is 40 Ω. The impedance and power factor are:
Show answer
Answer: B — 50 Ω and 0.6
Z = √(30² + 40²) = 50 Ω, and the power factor is R ÷ Z = 30 ÷ 50 = 0.6. Adding the resistance and reactance (70) is the usual slip, and 0.8 would be X ÷ Z, which is sin φ.A four-pole three-phase induction motor is supplied at 50 Hz and runs at 1,440 rpm. The slip is:
Show answer
Answer: D — 4%
Synchronous speed is 120 × 50 ÷ 4 = 1,500 rpm, so slip = (1,500 − 1,440) ÷ 1,500 = 0.04 = 4%. The rotor frequency is then 4% of 50 Hz = 2 Hz.A DC motor on a 220 V supply draws 20 A and has an armature resistance of 0.5 Ω. Its back EMF at that load is:
Show answer
Answer: A — 210 V
Eb = V − IaRa = 220 − 20 × 0.5 = 210 V. The 10 V is the armature drop and 230 V adds it instead of subtracting.A transformer delivers 4,000 W, with an iron loss of 100 W and a copper loss of 150 W. Its efficiency is about:
Show answer
Answer: C — 94.1%
Input = 4,000 + 100 + 150 = 4,250 W, so efficiency = 4,000 ÷ 4,250 = 94.1%. Counting only the copper loss would give 96.4%, and only the iron loss 97.6%.A three-phase load is supplied at a line voltage of 415 V and draws a line current of 10 A at a power factor of 0.8. The real power is about:
Show answer
Answer: B — 5,750 W
P = √3 × 415 × 10 × 0.8 ≈ 5,750 W. The 7,188 W figure is the apparent power (√3 × 415 × 10) without the power factor, and 3,320 W forgets the √3.A series circuit has a resistance of 8 Ω, an inductive reactance of 12 Ω and a capacitive reactance of 6 Ω. Connected to 100 V AC, the current drawn is:
Show answer
Answer: A — 10 A
Net reactance = 12 − 6 = 6 Ω, so Z = √(8² + 6²) = 10 Ω and I = 100/10 = 10 A. Adding the reactances (18 Ω) gives Z ≈ 19.7 Ω and 5 A, forgetting that XL and XC oppose each other.A single-phase load draws 5 A from a 230 V supply at a power factor of 0.8. The real power consumed is:
Show answer
Answer: A — 920 W
P = V I cos φ = 230 × 5 × 0.8 = 920 W. The product V × I = 1,150 is the apparent power in VA, not the real power in watts.An ideal transformer steps 440 V down to 220 V and the primary has 1,000 turns. If the primary current is 5 A, the number of secondary turns and the secondary current are respectively:
Show answer
Answer: A — 500 turns and 10 A
Turns ratio N₂ = 1,000 × 220/440 = 500. Power is conserved, so the current rises as the voltage falls: I₂ = 5 × 440/220 = 10 A. A step-down transformer has the larger current on the secondary.In a balanced star-connected three-phase system the phase voltage is 230 V. The line voltage is nearly:
Show answer
Answer: A — 398 V
In star, V_L = √3 × V_ph = 1.732 × 230 ≈ 398 V (the familiar 400 V supply). Dividing by √3 (133 V) is for finding phase from line voltage.The synchronous speed of a 6-pole three-phase induction motor on a 50 Hz supply is:
Show answer
Answer: A — 1,000 rpm
Ns = 120 f / P = 120 × 50 / 6 = 1,000 rpm. The speeds 1,500, 750 and 3,000 rpm belong to 4, 8 and 2 poles respectively.Consider the following statements about transformers:
1. A transformer works only with alternating supply.
2. Its efficiency is maximum when the copper loss equals the iron loss.
Which of the statements is/are correct?Show answer
Answer: A — Both 1 and 2
Mutual induction needs a changing flux, so a DC supply produces no secondary voltage. Maximum efficiency occurs at the load where the variable copper loss equals the constant iron loss. Both statements are correct.In a Wheatstone bridge, the arms P = 100 Ω, Q = 200 Ω and R = 50 Ω. For the bridge to be balanced, the fourth arm S must be:
Show answer
Answer: A — 100 Ω
Balance requires P/Q = R/S, so S = R × Q/P = 50 × 200/100 = 100 Ω. Using S = R × P/Q gives 25 Ω, which inverts the ratio.A 100 W lamp is rated for 220 V. The resistance of its filament when it works at the rated voltage is:
Show answer
Answer: C — 484 Ω
R = V² ÷ P = 220² ÷ 100 = 48,400 ÷ 100 = 484 Ω. Check: current 100 ÷ 220 = 0.4545 A and 220 ÷ 0.4545 = 484. Using V ÷ P gives the tempting 2.2.Kirchhoff's current law states that at any node:
Show answer
Answer: A — The algebraic sum of the currents is zero
KCL is conservation of charge: current in equals current out. The voltage statement is Kirchhoff's voltage law around a loop, the tempting twin.A 2 kW heater runs for 3 hours a day for 30 days. At ₹7 a unit the cost of the energy for the month is:
Show answer
Answer: D — ₹1,260
Energy = 2 × 3 × 30 = 180 kWh, and 180 × 7 = ₹1,260. The ₹42 is the cost for one day only.Consider the following statements about power factor:
1. For the same real power, a lower power factor makes the load draw more current.
2. A capacitor connected in parallel with an inductive load improves its lagging power factor.
Which of the statements given above is/are correct?Show answer
Answer: A — Both 1 and 2
I = P ÷ (V cos φ), so a low power factor needs more current, and a parallel capacitor supplies the reactive current. A series inductor would worsen it, the tempting wrong device.In a balanced delta-connected three-phase load the phase current is 10 A. The line current is about:
Show answer
Answer: C — 17.3 A
In delta, line current = √3 × phase current = 1.732 × 10 = 17.3 A. The 10 A is the star relation, where the two currents are equal, the tempting mix-up.A 50 Hz transformer has 500 primary turns and a peak core flux of 0.002 Wb. Using E = 4.44 f N Φm, the primary induced EMF is about:
Show answer
Answer: D — 222 V
E = 4.44 × 50 × 500 × 0.002 = 222 V. Check: 4.44 × 50 = 222 and 500 × 0.002 = 1. Forgetting the 4.44 factor gives the tempting 50 V.In a DC shunt motor, if the field flux is reduced while the supply voltage stays constant, the speed:
Show answer
Answer: C — Rises, since speed is roughly proportional to Eb ÷ flux
Speed N ∝ Eb ÷ Φ, so weakening the field raises the speed, which is why a broken field circuit can make a shunt motor race. Falling speed is the tempting guess from falling torque.A 4-pole alternator is driven at 1,500 rpm. The frequency of the generated voltage is:
Show answer
Answer: D — 50 Hz
f = P N ÷ 120 = 4 × 1,500 ÷ 120 = 50 Hz. Check: 1,500 rpm is 25 rev/s and 2 pole pairs give 50 cycles/s. Using P ÷ 2 incorrectly gives 25.The main purpose of earthing the metal body of an electrical appliance is to:
Show answer
Answer: B — Give leakage current a safe path to earth, protecting the user from shock
A fault current flows through the low-resistance earth wire and trips the fuse or breaker instead of passing through the user. It does not change power use, the tempting claim.Assertion (A): Transformers are rated in kVA and not in kW.
Reason (R): The copper loss depends on the current and the iron loss on the voltage, and neither depends on the power factor of the load.
Which one of the following is correct?Show answer
Answer: A — Both A and R are true, and R is the correct explanation of A
Losses depend on V and I, so the heating limit is a kVA limit whatever the power factor, and R explains A. Quoting kW would understate the loading at low power factor.