Moist Air and Psychrometry, Hydraulic Turbines, Pumps and Compressors
The Psychrometric Chart and the Basic Processes
The chart plots ω against dry-bulb temperature with lines of constant φ, h, wet-bulb temperature and specific volume. Sensible heating or cooling is a horizontal line (ω constant, dew point constant). Cooling and dehumidification crosses the dew point: the air leaving the coil is near-saturated at the coil surface temperature. Cool the 0.01604 kg/kg air at 30 °C to saturated air at 12 °C (p_g = 1.403 kPa): ω₂ = 0.00873, h₂ = 34.1 kJ/kg, condensate 7.31 g per kg dry air, and the coil removes h₁ − h₂ − (ω₁ − ω₂) h_w = 36.7 kJ/kg dry air, of which the sensible heat factor SHF = sensible/total = 0.50 — about half of the load is latent here, and the share grows as the air gets more humid. Humidification by steam moves the state upward and slightly to the right; by an adiabatic water spray it follows a constant-wet-bulb line (h nearly constant), which is evaporative cooling: dry-bulb falls as ω rises, and it works only in dry climates, since it can only approach the wet-bulb temperature.
Adiabatic mixing of two streams is a straight line on the chart, and the mixed state divides it in the inverse ratio of the dry-air masses: ω₃ = (m_a1 ω₁ + m_a2 ω₂)/(m_a1 + m_a2), h₃ likewise. Mixing 3 kg/s of the 30 °C air with 1 kg/s of the cooled air gives ω₃ = 0.01422 and h₃ = 61.9 kJ/kg — three-quarters of the way towards stream 1. Mixing two unsaturated streams can produce a fog if the straight line crosses the saturation curve, because the curve is concave. Air-conditioning is the use of these processes: summer cooling is cool-and-dehumidify then reheat to comfort; winter is preheat, humidify, reheat. The comfort range is conventionally around 22–26 °C and 40–60% RH.
- Sensible heating or coolingHorizontal line; ω constant
- Cooling and dehumidificationCrosses the dew point
- Humidification by steamUpward, slightly right
- Evaporative coolingConstant wet-bulb; dry climates only
The chart plots ω against dry-bulb temperature with lines of constant φ, h, wet-bulb temperature and specific volume. Sensible heating or cooling is a horizontal line (ω constant, dew point…
Impulse and Reaction: Pelton, Francis and Kaplan Turbines
Water power is P = ρ g Q H η; at Q = 0.5 m³/s, H = 400 m and 90% overall efficiency that is 1766 kW. Pelton wheel (impulse): a nozzle converts the entire head to a jet of speed V = C_v √(2 g H) (C_v ≈ 0.98: 86.8 m/s at 400 m), the jet strikes split buckets on the rim, and the wheel runs at atmospheric pressure. Per unit mass the work is u (V − u)(1 + k cos β), so for a bucket that reverses the jet the efficiency 4 (u/V)(1 − u/V) peaks when u = V/2; in practice the bucket speed ratio is about 0.45 because the jet cannot be turned a full 180° and friction acts. It suits high head and low flow. Francis (reaction, mixed flow): water enters radially inward through guide vanes, turns axial, and part of the head is still pressure in the runner; a draft tube below recovers the exit kinetic energy and keeps the runner pressure below atmospheric, which is also what exposes it to cavitation. It suits medium head. Kaplan (reaction, axial): a propeller with adjustable runner blades and adjustable guide vanes, which holds efficiency across a wide flow range; low head, high flow.
| Turbine | Type and flow | Head / flow | Specific speed N_s (indicative, kW–m–rpm) |
|---|---|---|---|
| Pelton | Impulse, tangential jet | High head, low flow | roughly 10–60 |
| Francis | Reaction, radial-to-axial | Medium head, medium flow | roughly 60–300 |
| Kaplan | Reaction, axial | Low head, high flow | roughly 300–1000 |
Specific speed N_s = N √P / H^(5/4) (P in kW, H in m, N in rpm) is the speed of a geometrically similar turbine that makes 1 kW under 1 m head, and it picks the family: a 600 rpm, 3000 kW wheel at 400 m has N_s = 18.4, firmly Pelton. Unit quantities N_u = N/√H, Q_u = Q/√H, P_u = P/H^(3/2) scale a model to a prototype. Cavitation occurs where local pressure falls to the vapour pressure, at the runner exit of reaction turbines; the Thoma coefficient σ = (H_atm − H_v − H_s)/H must exceed a critical value, which is why a low-head Kaplan is set deep.
- Impulse
- Pelton wheel: high head, low flow
- Reaction
- Francis (mixed flow): medium head
- Kaplan (axial): low head, high flow

Water power is P = ρ g Q H η; at Q = 0.5 m³/s, H = 400 m and 90% overall efficiency that is 1766 kW. Pelton wheel (impulse): a nozzle converts the entire head to a jet of speed V = C_v √(2…
Pumps, Pump Characteristics and Air Compressors
A centrifugal pump delivers head by the Euler equation, H_th = (u₂V_w2 − u₁V_w1)/g, less losses. Its characteristic curve falls with flow; the system curve H = H_static + K Q² rises; the pump runs where they cross. Affinity laws at the same geometry and fluid: Q ∝ N, H ∝ N², P ∝ N³ — slowing a pump to 80% of speed gives 80% flow, 64% head and 51.2% power, which is why a speed control saves so much energy. Two identical pumps in series add heads at the same flow; in parallel they add flows at the same head (but the result is less than double on a steep system curve). Pump specific speed is N_s = N √Q / H^(3/4) (Q in m³/s, H in m, N in rpm): 1450 rpm, 0.05 m³/s, 30 m gives 25.3, a radial-flow machine. NPSH available (suction head above vapour pressure) must exceed NPSH required or the pump cavitates: noise, vibration, falling head and pitted impellers.
Reciprocating compressor. Work per cycle for a polytropic compression P V^n = const from P₁ to P₂ is W = n/(n−1) · P₁V₁ [(P₂/P₁)^((n−1)/n) − 1], and for isothermal compression W = P₁V₁ ln(P₂/P₁), the minimum. Taking intake 100 kPa × 0.1 m³ compressed to 900 kPa with n = 1.3: single stage 28.62 kJ against 21.97 kJ isothermal. Splitting into two stages with perfect intercooling at the optimum intermediate pressure P_i = √(P₁P₂) = 300 kPa (pressure ratio 3.00 per stage) costs 25.01 kJ, a 12.6% saving; in general the best ratio per stage is (P_final/P₁)^(1/N). The clearance volume wastes a fraction of the stroke: η_vol = 1 + C − C (P₂/P₁)^(1/n), and with C = 0.05 and ratio 9 it is 77.9%. Clearance does not change the work per kg delivered (the re-expansion returns its energy) but cuts the capacity, so it matters at high pressure ratio, and is a reason for multi-staging.
A centrifugal pump delivers head by the Euler equation, H_th = (u₂V_w2 − u₁V_w1)/g, less losses. Its characteristic curve falls with flow; the system curve H = H_static + K Q² rises; the…
Key takeaways
- Moist-air properties are per kg DRY air: ω = 0.622 p_v/(P − p_v), φ = p_v/p_g, h = 1.005T + ω(2501 + 1.88T); T_dry ≥ T_wet ≥ T_dew, all equal at saturation.
- Sensible change is horizontal on the chart; cooling below the dew point removes m_a(ω₁ − ω₂) of water; evaporative cooling follows a constant wet-bulb line; mixing is a straight line divided by the dry-air masses.
- Pelton = impulse, high head, jet speed C_v√(2gH), best bucket speed ≈ half the jet speed; Francis = mixed-flow reaction with draft tube, medium head; Kaplan = axial reaction with adjustable blades, low head.
- Specific speed picks the machine family; affinity laws Q ∝ N, H ∝ N², P ∝ N³; NPSH available must exceed NPSH required to avoid cavitation; the operating point is where pump and system curves cross.
- Compressor work is least isothermal; multistage with intercooling uses P_i = √(P₁P₂) for two stages; clearance cuts capacity (η_vol = 1 + C − C r^(1/n)) but not work per kg.
Practice questions (24)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
The humidity ratio of moist air is defined as:
Show answer
Answer: C — mass of water vapour per unit mass of dry air
ω = m_v/m_a = 0.622 p_v/(P − p_v), referred to DRY air because dry air is the component that does not enter or leave the process. p_v/p_g is the relative humidity.Air at 30 °C, 60% relative humidity, total pressure 101.325 kPa, saturation pressure at 30 °C taken as 4.246 kPa. The humidity ratio is nearest to:
Show answer
Answer: A — 0.0160 kg/kg
p_v = 0.6 × 4.246 = 2.548 kPa and ω = 0.622 × 2.548/(101.325 − 2.548) = 0.01604. The 0.0255 option is p_v in kPa mistaken for ω.Moist air is cooled at constant pressure and constant humidity ratio until water first appears. The temperature reached is the:
Show answer
Answer: D — dew-point temperature
Dew point is by definition the temperature where p_g(T) = p_v, reached along a horizontal line on the chart. The wet-bulb temperature is higher than the dew point unless the air is already saturated.
Show the other 21 questions
Which ordering of temperatures holds for unsaturated moist air?
Show answer
Answer: A — dry-bulb > wet-bulb > dew-point
Evaporation cools the wet wick below the dry-bulb, but only until the wick air is saturated, so the wet-bulb stays above the dew point of the surrounding air. All three coincide only at 100% relative humidity.Which turbine is an impulse machine working at atmospheric pressure?
Show answer
Answer: B — Pelton wheel
Only the Pelton converts the whole head into a free jet before the wheel, so the buckets see atmospheric pressure. Francis and Kaplan have pressure drop inside the runner and need a draft tube.A Pelton nozzle has C_v = 0.98 under a net head of 400 m. Find the jet velocity in m/s (nearest integer).
Numerical answer — type the value.
Show answer
Answer: 87
V = C_v √(2 g H) = 0.98 × √(2 × 9.81 × 400) = 0.98 × 88.59 = 86.8 m/s. Dropping the velocity coefficient would give 88.6 m/s.A turbine runs at 600 rpm, produces 3000 kW under a head of 400 m. Its specific speed N√P/H^(5/4) is nearest to:
Show answer
Answer: A — 18
N_s = 600 × √3000 / 400^1.25 = 600 × 54.77 / 1788.9 = 18.4 — in the Pelton range, as expected for 400 m head.A pump is slowed to 80% of its speed (same impeller, same fluid). By the affinity laws the head and the power become respectively:
Show answer
Answer: C — 64% and 51.2%
H ∝ N² gives 0.8² = 0.64 and P ∝ N³ gives 0.8³ = 0.512; flow falls to 80%. The cube law on power is the energy argument for variable-speed drives.A two-stage reciprocating air compressor with perfect intercooling delivers from 1 bar to 9 bar. The ideal intermediate pressure for minimum work is:
Show answer
Answer: B — 3 bar
Minimum work with equal intercooled stages needs equal pressure ratios, P_i = √(P₁P₂) = √9 = 3 bar, i.e. 3 per stage. The arithmetic mean 5 bar is the common wrong guess.Moist air has a water-vapour partial pressure of 1.5 kPa while the saturation pressure at its temperature is 3.0 kPa. The relative humidity, in per cent, is ____.
Numerical answer — type the value.
Show answer
Answer: 50
φ = p_v/p_g = 1.5/3.0 = 0.5, i.e. 50 %. Using p_v/p_total would give a very small, wrong value. Substituting the answer back into the relation confirms it.Moist air at 101.325 kPa has a vapour partial pressure of 2 kPa. The humidity ratio ω = 0.622 p_v/(p − p_v), to four decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 0.0125
ω = 0.622 × 2/(101.325 − 2) = 1.244/99.325 = 0.0125 kg/kg dry air. Using p instead of (p − p_v) in the denominator gives 0.0123.A Pelton nozzle with velocity coefficient 0.98 works under a net head of 100 m (g = 9.81 m/s²). The jet velocity C_v√(2gH), in m/s to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 43.4
V = 0.98 × √(2 × 9.81 × 100) = 0.98 × 44.3 = 43.4 m/s. Dropping C_v gives the ideal 44.3 m/s. Substituting the answer back into the relation confirms it.A pump of overall efficiency 60 % delivers 0.01 m³/s of water against a head of 30 m. The shaft power ρgQH/η, in kW to three decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 4.905
P = 1000 × 9.81 × 0.01 × 30/0.6 = 4905 W = 4.905 kW; the water power alone is 2.943 kW. Multiplying by η instead of dividing gives 1.77 kW.A Kaplan turbine is best suited to sites with:
Show answer
Answer: A — low head and very large flow
A Kaplan (axial-flow, adjustable-blade) turbine has high specific speed and suits low heads with large discharge. High head, small flow is the Pelton regime.A pump delivers 0.05 m³/s at 1000 rpm. By the affinity laws, at 1500 rpm (same impeller) the flow, in m³/s, is ____.
Numerical answer — type the value.
Show answer
Answer: 0.075
Flow is proportional to speed: Q₂ = 0.05 × 1500/1000 = 0.075 m³/s. Squaring the ratio (0.1125) applies to head, not flow.A pump develops a head of 20 m at its rated speed. By the affinity laws, at 1.2 times that speed the head, in m, is ____.
Numerical answer — type the value.
Show answer
Answer: 28.8
Head scales with speed squared: 20 × 1.2² = 28.8 m. Scaling linearly (24 m) applies to flow, not head. Substituting the answer back into the relation confirms it.Moist air at 30 °C with humidity ratio 0.012 has specific enthalpy h = 1.005T + ω(2501 + 1.88T), in kJ per kg of dry air to one decimal place, of ____.
Numerical answer — type the value.
Show answer
Answer: 60.8
h = 30.15 + 0.012 × (2501 + 56.4) = 30.15 + 30.69 = 60.8 kJ/kg dry air. Dropping the latent term gives only the dry-air value 30.2.A water jet of mass flow 50 kg/s moves at 80 m/s. Its kinetic power ½ ṁ V², in kW, is ____.
Numerical answer — type the value.
Show answer
Answer: 160
P = 0.5 × 50 × 80² = 160 000 W = 160 kW. Using ṁ V² (320 kW) forgets the ½ of kinetic energy. Substituting the answer back into the relation confirms it.A compressor handles 0.1 m³/s of air at 100 kPa and compresses it isothermally to 800 kPa. The ideal power p₁V̇₁ ln(p₂/p₁), in kW to two decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 20.79
P = 100 × 0.1 × ln 8 = 10 × 2.079 = 20.79 kW (kPa·m³/s = kW). Using the pressure difference (700 × 0.1 = 70 kW) would overstate the work.Two moist-air streams are mixed adiabatically: 2 kg/s of dry air with humidity ratio 0.008 and 1 kg/s of dry air with humidity ratio 0.020. The mixed humidity ratio, to three decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 0.012
Vapour is conserved, weighted by dry-air flows: ω = (2 × 0.008 + 1 × 0.020)/3 = 0.012. The simple average (0.014) ignores the 2:1 flow ratio.A pump runs at 1450 rpm and delivers 0.05 m³/s at a head of 20 m. Its specific speed N_s = N√Q/H^(3/4) (SI units), to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 34.3
N_s = 1450 × √0.05/20^0.75 = 1450 × 0.2236/9.457 = 34.3, a radial (centrifugal) pump. Using H^(5/4) (the turbine form) in the denominator would give a much smaller number.Moist air flows at 1 kg/s of dry air through a cooling coil, entering at h₁ = 70 kJ/kg and leaving at h₂ = 45 kJ/kg, with 0.003 kg/s of condensate removed at an enthalpy of 84 kJ/kg. The cooling load ṁ(h₁ − h₂) − ṁ_w h_w, in kW to two decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 24.75
Energy balance: Q = 1 × (70 − 45) − 0.003 × 84 = 25 − 0.252 = 24.75 kW. Quoting 25 kW ignores the enthalpy carried off by the condensate.A Pelton wheel receives a jet of 0.1 m³/s at 60 m/s. The buckets move at 25 m/s and turn the relative jet through 165° (so the relative velocity is deflected back by 15° from reversal). Using F = ρQ(V − u)(1 + cos 15°), the power delivered to the wheel F u, in kW to the nearest integer, is ____.
Numerical answer — type the value.
Show answer
Answer: 172
F = 1000 × 0.1 × 35 × (1 + 0.9659) = 6881 N, so P = F u = 6881 × 25 = 172 kW. A full 180° reversal (cos 0 = 1) would give 175 kW, while using V instead of V − u overstates the force.A two-stage compressor handles 0.1 m³/s of air at 100 kPa (p₁V̇₁ = 10 kW) and delivers at 1600 kPa with perfect intercooling and polytropic index n = 1.3 in both stages. With the optimum intermediate pressure, the work W = 2 [n/(n − 1)] p₁V̇₁ [(p₂/p₁)^((n−1)/2n) − 1], in kW to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 32.7
With p_i = √(100 × 1600) = 400 kPa the exponent is 0.3/2.6 = 0.1154, giving 16^0.1154 = 1.377 and W = 2 × 4.333 × 10 × 0.377 = 32.7 kW. Single-stage compression to 1600 kPa would need 1.3/0.3 × 10 × (16^0.2308 − 1) = 38.8 kW, so intercooling saves work.