Power Systems III: Symmetrical-Component Arithmetic, Unsymmetrical Faults (LG, LL, LLG), Overcurrent, Differential and Distance Protection, Circuit Breakers and Equal-Area Stability

Section 6 of the EE paper asks for symmetrical components, symmetrical and unsymmetrical fault analysis, the principles of overcurrent, differential, directional and distance protection, circuit breakers and the equal-area criterion — and the first chapter gave the unsymmetrical faults a table of connections and the protection a table of principles, with no arithmetic. This chapter does the arithmetic. Resolve the unbalanced currents 10∠0°, 10∠−90° and 0 A and the positive-sequence part is 6.440∠15.0° A. For a 20 MVA, 11 kV generator with X₁ = X₂ = 0.2 and X₀ = 0.1 pu the three-phase fault current is 5.00 pu, the LL fault 4.33 pu, the single line-to-ground fault 6.00 pu and the double line-to-ground fault 7.50 pu — so, because X₀ < X₁, the earth faults exceed the three-phase fault. A 4000 A fault on a relay set at 400 A pickup (plug-setting multiplier 10) operates an IDMT relay in 2.97 × TMS seconds. A swing of 5 MJ/MVA holding 0.8 pu through a fault whose Pmax is 2 pu must clear in about 0.30 s.
Overview

Symmetrical Components: Resolving and Recombining

1 min read

Any three unbalanced phasors (I_a, I_b, I_c) are the sum of a positive-sequence set (equal magnitude, 120° apart, phase order a-b-c), a negative-sequence set (equal magnitude, order a-c-b) and a zero-sequence set (three equal, in-phase phasors). With the operator a = 1∠120° (a² = 1∠240°, 1 + a + a² = 0): I_a0 = (I_a + I_b + I_c)/3, I_a1 = (I_a + aI_b + a²I_c)/3, I_a2 = (I_a + a²I_b + aI_c)/3, and back, I_a = I_a0 + I_a1 + I_a2, I_b = I_a0 + a²I_a1 + aI_a2, I_c = I_a0 + aI_a1 + a²I_a2. Example: I_a = 10∠0°, I_b = 10∠−90°, I_c = 0: I_a0 = (10 − j10)/3 = 4.714∠-45.0°, I_a1 = 6.440∠15.0°, I_a2 = 1.725∠75.0°; check I_a0 + I_a1 + I_a2 = 10∠0° and I_c = I_a0 + aI_a1 + a²I_a2 = 0. The zero-sequence current is one-third of the neutral current (I_n = 3I_a0), so it exists only when there is a path to earth. A balanced set has only I_a1; a single-phase load draws equal I₀, I₁, I₂ = I/3 each. Power is the same in either frame: S = V_aI_a* + V_bI_b* + V_cI_c* = 3(V_a0I_a0* + V_a1I_a1* + V_a2I_a2*).

SequencePhase orderPresent inImpedance of generator
Positivea-b-cAll faults, normal operationZ₁ = synchronous / transient / subtransient reactance
Negativea-c-bUnbalanced faults and loadsZ₂ ≈ subtransient (smaller than Z₁ at steady state)
ZeroIn phaseFaults involving earthZ₀ small; includes 3Z_n of any neutral impedance

Any three unbalanced phasors (I_a, I_b, I_c) are the sum of a positive-sequence set (equal magnitude, 120° apart, phase order a-b-c), a negative-sequence set (equal magnitude, order a-c-b)…

Sequence Networks and the Four Fault Connections

2 min read · 3 parts

Each component has three sequence impedances. Static elements (lines, transformers) have Z₁ = Z₂; rotating machines do not (Z₂ ≠ Z₁), and a machine has a small Z₀. Transformer zero-sequence path: Y-grounded to Y-grounded passes zero sequence; a delta winding provides a closed circulating path for it (so the zero-sequence network connects the delta to the reference bus — I₀ circulates inside the delta but never reaches the line); ungrounded Y blocks it. An earthed neutral impedance Z_n enters the zero-sequence network as 3Z_n. Zero-sequence reactance of a line is 2–3.5 times its positive-sequence value. The four connections at the fault point F, with Thevenin voltage E (prefault) and driving-point impedances Z₁, Z₂, Z₀ and fault impedance Z_f:

FaultSequence networksI_a1Fault current
Three-phasePositive onlyE/(Z₁ + Z_f)I_f = E/(Z₁ + Z_f)
Single line-to-ground (a-g)All three in seriesE/(Z₁ + Z₂ + Z₀ + 3Z_f)I_f = 3I_a1
Line-to-line (b-c)Positive and negative in parallelE/(Z₁ + Z₂ + Z_f)I_b = −I_c = −j√3 I_a1
Double line-to-ground (b-c-g)All three in parallelE/(Z₁ + Z₂(Z₀ + 3Z_f)/(Z₂ + Z₀ + 3Z_f))I_f = 3I_a0

Worked: a 20 MVA, 11 kV generator, X₁ = X₂ = 0.2, X₀ = 0.1 pu, E = 1 pu, solidly grounded, fault at the terminals. Base current = 20 × 10⁶/(√3 × 11 000) = 1050 A. Three-phase: I_f = 1/0.2 = 5.00 pu = 5249 A (short-circuit level 20/0.2 = 100 MVA). Line-to-ground: I_a1 = I_a2 = I_a0 = 1/(0.2 + 0.2 + 0.1) = 2 pu, I_f = 3I_a0 = 6.00 pu = 6298 A; the healthy-phase voltages rise to |V_b| = 0.92 pu, |V_c| = 0.92 pu. Line-to-line: I_a1 = −I_a2 = 1/0.4 = 2.5 pu, |I_b| = √3 × 2.5 = 4.33 pu = 4545 A and no zero-sequence current (the LL current is 0.866 of the three-phase value, always). Double line-to-ground: X₂‖X₀ = 0.2 × 0.1/0.3 = 0.0667; I_a1 = 1/(0.2 + 0.0667) = 3.75 pu; I_a0 = −I_a1X₂/(X₂ + X₀) = 2.50 pu in magnitude; earth current I_f = 3I_a0 = 7.50 pu = 7873 A. Fault impedance: with Z_f = 0.1 pu resistive in the LG case, I_f = 3/|j0.5 + 0.3| = 5.14 pu. Neutral reactor: X_n = 0.05 pu raises Z₀ to 0.1 + 3 × 0.05 = 0.25 and cuts I_f(LG) to 3/0.65 = 4.62 pu — the purpose of grounding impedance.

⚠️ Which fault is largest depends on X₀
LG exceeds three-phase when X₀ < X₁ (here 6 pu against 5 pu); LLG exceeds both when X₀ is small; with high X₀ (ungrounded or high-impedance earth) the LG current is tiny. A breaker is rated on the larger of the three-phase and earth-fault duty — never assume the three-phase fault is worst.
Transformer zero-sequence paths
Zero-sequence current
  • Grounded Y to grounded YPasses it
  • Delta windingCirculates inside; connects to reference bus
  • Ungrounded YBlocks it

Each component has three sequence impedances. Static elements (lines, transformers) have Z₁ = Z₂; rotating machines do not (Z₂ ≠ Z₁), and a machine has a small Z₀. Transformer zero-sequence…

Protection: Overcurrent, Differential, Directional and Distance

2 min read · 2 parts

Overcurrent relay. Pick-up current = plug setting (PS) × CT secondary rating; the plug-setting multiplier PSM = (fault current in the relay)/(pick-up current) = I_f/(PS × I_CT-primary). An IEC standard inverse relay operates in t = TMS × 0.14/(PSM⁰·⁰² − 1) seconds (very inverse: 13.5/(PSM − 1); extremely inverse: 80/(PSM² − 1)), where TMS (time-multiplier setting) scales the curve. Example: CT 400/5, PS = 100% (400 A primary pick-up), fault 4000 A: PSM = 10, t = TMS × 0.14/(10⁰·⁰² − 1) = 2.97 × TMS s, so TMS = 0.1 gives 0.297 s. Coordination: the upstream relay (CT 800/5, TMS 0.2) sees PSM = 5.0 and operates in 0.86 s, a margin of 0.56 s over the downstream relay — a grading margin of 0.3–0.5 s covers the breaker time and relay over-travel. The price of time-graded protection is that the relay nearest the source is slowest to clear the most severe fault.

Differential protection compares the currents entering and leaving a zone (transformer, generator, bus): the operating current is |I₁ − I₂| and the restraining current (I₁ + I₂)/2; a percentage-differential relay trips when |I₁ − I₂| > k(I₁ + I₂)/2 (slope 10–40%), which tolerates CT mismatch and tap-changer error and the inrush harmonics of a transformer (blocked by second-harmonic restraint). CT ratios on a Δ–Y transformer are connected Y–Δ so the secondary currents are in phase. Directional elements decide the sign of power flow (phase between V and I) and make overcurrent protection work in a ring or parallel feeders. Distance (impedance) protection measures Z = V/I at the relay, proportional to the distance to the fault for a uniform line. The secondary impedance is Z_sec = Z_prim × (CT ratio)/(VT ratio): a 100 km line at 0.4 Ω/km is 40 Ω primary; with CT 1000/5 (200) and VT 220 kV/110 V (2000), Z_sec = 40 × 200/2000 = 4.0 Ω. Zone 1 covers 80% of the line (not 100%, to avoid over-reach on CT/VT errors) = 3.2 Ω, instantaneous; zone 2 reaches 120% of the line (or the line plus 50% of the next), with a 0.3–0.5 s delay; zone 3 is back-up for the next line. Distance relays are unaffected by changing source impedance, which is why they are the choice on transmission lines.

RelayQuantitySelectivityTypical use
Overcurrent (IDMT)I_f/pick-up (PSM)Time graded (non-unit)Distribution feeders
Differential|I₁ − I₂| vs slopeUnit protection, absoluteTransformers, generators, buses
DirectionalPhase of V and IAdds directionRing mains, parallel lines
DistanceZ = V/IZones 80%, 120%, back-upTransmission lines

Overcurrent relay. Pick-up current = plug setting (PS) × CT secondary rating; the plug-setting multiplier PSM = (fault current in the relay)/(pick-up current) = I_f/(PS × I_CT-primary). An…

Circuit Breaker Ratings and Equal-Area Stability

2 min read · 3 parts

Breaker ratings. Rated breaking capacity is the symmetrical rms current the breaker can interrupt at rated voltage; in MVA it is √3 × V_kV × I_kA: 11 kV and 31.5 kA give 600 MVA. Making capacity is the peak of the first cycle of the asymmetrical current and is about 2.55 × the symmetrical breaking current (2.55 × 31.5 = 80.3 kA peak), because of the DC offset. Short-time rating is the rms current carried for 1–3 s. The breaker must also handle the restriking voltage and its rate of rise (RRRV) after current zero, set by the system L and C. Arc quenching: SF₆ (high dielectric strength, electronegative), vacuum (arc extinguished at the first current zero), air-blast, oil (minimum-oil, bulk-oil). A fuse is the simplest breaker; an isolator has no breaking capacity and must be opened only with no current.

Equal-area criterion. For a machine on an infinite bus, P_e = P_max sin δ and the swing equation (M d²δ/dt² = P_m − P_e) gives stability if the accelerating area A₁ = ∫(P_m − P_e,fault)dδ from δ₀ to δ_c does not exceed the decelerating area A₂ = ∫(P_e,post − P_m)dδ from δ_c to δ_max, where δ_max = π − arcsin(P_m/P_max,post). Take P_m = 0.8 pu, pre-fault P_max = 2.0 (δ₀ = arcsin 0.4 = 23.58°), fault P_max = 0.5, post-fault P_max = 1.5 (δ_max = 147.77°). Setting A₁ = A₂ gives cos δ_c = [P_m(δ_max − δ₀) + P₃cos δ_max − P₂cos δ₀]/(P₃ − P₂), so δ_c = 89.6°. For a terminal three-phase fault (P₂ = 0, post-fault = pre-fault): cos δ_c = (P_m/P_max)(π − 2δ₀) − cos δ₀ = 0.0109, δ_c = 89.4°, and with the fault-on swing δ = δ₀ + πf P_m t²/(2H), the critical clearing time t_c = √(2H(δ_c − δ₀)/(πf P_m)) = √(2 × 5 × 1.1484/(π × 50 × 0.8)) = 0.30 s (H = 5 MJ/MVA, 50 Hz). Faster clearing, a lower pre-fault P_m, higher voltage or reclosing all enlarge the margin.

QuantityFormulaWorked value
Breaking MVA√3 V I600 MVA (11 kV, 31.5 kA)
Making current≈ 2.55 × I_break80.3 kA peak
Critical clearing angle (terminal fault)cos δ_c = (P_m/P_max)(π − 2δ₀) − cos δ₀89.4°
Critical clearing time√(2H(δ_c − δ₀)/(πfP_m))0.30 s
Equal-area check, worked case
  1. Pre-fault δ₀ = 23.58°
  2. Fault on: accelerating area A₁δ₀ to δ_c
  3. Cleared at δ_c = 89.6°Critical: A₁ = A₂
  4. Decelerating area A₂δ_c to δ_max = 147.77°
P_m = 0.8 pu; P_max 2.0 pre-fault, 0.5 during, 1.5 after.

Breaker ratings. Rated breaking capacity is the symmetrical rms current the breaker can interrupt at rated voltage; in MVA it is √3 × V_kV × I_kA: 11 kV and 31.5 kA give 600 MVA. Making…

Key takeaways

  • Symmetrical components: I_a1 = (I_a + aI_b + a²I_c)/3, I_a2 = (I_a + a²I_b + aI_c)/3, I_a0 = (I_a + I_b + I_c)/3; neutral current = 3I_a0.
  • Fault currents: LLL = E/Z₁; LG = 3E/(Z₁ + Z₂ + Z₀ + 3Z_f); LL = √3E/(Z₁ + Z₂); LLG from Z₂‖Z₀. Neutral impedance enters as 3Z_n; a delta blocks zero sequence from the line.
  • LG exceeds three-phase when X₀ < X₁; never assume the three-phase fault is the worst.
  • IDMT relay: PSM = I_f/pick-up, t = TMS × 0.14/(PSM⁰·⁰² − 1); distance relay Z_sec = Z_prim × CT ratio/VT ratio, zone 1 at 80%; differential relays are unit protection.
  • Breaker breaking MVA = √3VI, making current ≈ 2.55 × breaking current; equal-area stability: A₁ ≤ A₂ and the critical clearing time follows from δ_c.

Practice questions (24)

Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.

  1. Phase currents I_a = 10∠0°, I_b = 10∠−90° A and I_c = 0 are resolved into symmetrical components. The zero-sequence current I_a0 has magnitude:

    1. 4.71 A
    2. 0
    3. 10 A
    4. 3.33 A
    Show answer

    Answer: A — 4.71 A

    I_a0 = (I_a + I_b + I_c)/3 = (10 − j10)/3 = 4.71∠−45° A. The neutral current is three times this, 14.1 A.
  2. A transformer with a delta winding and a grounded-star winding is connected in a system. For a zero-sequence current, the delta winding:

    1. blocks it completely, with no circulating current
    2. reverses its direction
    3. passes zero-sequence current freely to its line
    4. provides a closed circulating path but passes no zero-sequence current to its line
    Show answer

    Answer: D — provides a closed circulating path but passes no zero-sequence current to its line

    Zero-sequence currents are in phase in the three windings, so they circulate inside the delta but cannot leave through the lines. In the zero-sequence network the delta is therefore tied to the reference bus.
  3. A 20 MVA, 11 kV generator has X₁ = X₂ = 0.2 pu and X₀ = 0.1 pu (E = 1 pu). The single line-to-ground fault current at its terminals, in pu (two decimals), is:

    Numerical answer — type the value.

    Show answer

    Answer: 6.00

    I_f = 3E/(X₁ + X₂ + X₀) = 3/0.5 = 6.00 pu (6298 A), which exceeds the three-phase value 1/0.2 = 5 pu because X₀ is the smallest reactance.
Show the other 21 questions
  1. For the same generator, the line-to-line fault current at the terminals in pu (two decimals) is:

    Numerical answer — type the value.

    Show answer

    Answer: 4.33

    I_a1 = −I_a2 = 1/(0.2 + 0.2) = 2.5 pu; |I_b| = √3 × 2.5 = 4.33 pu, which is 0.866 of the three-phase current (5 pu).
  2. For the same generator, a double line-to-ground fault at the terminals carries an earth current 3I_a0 of (pu, two decimals):

    Numerical answer — type the value.

    Show answer

    Answer: 7.50

    X₂‖X₀ = 0.0667; I_a1 = 1/(0.2 + 0.0667) = 3.75; I_a0 = I_a1X₂/(X₂ + X₀) = 2.50 in magnitude; 3I_a0 = 7.50 pu.
  3. An IDMT relay (t = TMS × 0.14/(PSM⁰·⁰² − 1)) has a CT of 400/5 and a plug setting of 100%. For a fault current of 4000 A and TMS = 0.1, the operating time in seconds (two decimals) is:

    Numerical answer — type the value.

    Show answer

    Answer: 0.30

    PSM = 4000/400 = 10; t = 0.1 × 0.14/(10⁰·⁰² − 1) = 0.1 × 2.971 = 0.297 s.
  4. Zone 1 of a distance relay is normally set to cover about:

    1. 100% of the line plus the whole next line
    2. 50% of the line
    3. 80% of the protected line, with no intentional delay
    4. 120% of the line with a time delay
    Show answer

    Answer: C — 80% of the protected line, with no intentional delay

    Setting zone 1 short of 100% prevents over-reach from CT, VT and line-impedance errors into the next line; zone 2 (120%, delayed) covers the remaining 20%.
  5. Which statements about power-system protection are correct?

    1. A percentage-differential relay uses a restraining current to tolerate CT mismatch
    2. A distance relay's reach depends strongly on the source impedance
    3. Differential protection is unit protection and is selective by definition of its zone
    4. Overcurrent relays are coordinated by grading their time settings
    Show answer

    Answer: A — A percentage-differential relay uses a restraining current to tolerate CT mismatch; C — Differential protection is unit protection and is selective by definition of its zone; D — Overcurrent relays are coordinated by grading their time settings

    A distance relay measures V/I at the relay, so its reach depends on line impedance, not on the source behind it — the reason it is preferred on transmission lines.
  6. A circuit breaker rated at 31.5 kA symmetrical breaking current has a making current of about 2.55 times that, in kA peak (one decimal):

    Numerical answer — type the value.

    Show answer

    Answer: 80.3

    2.55 × 31.5 = 80.3 kA peak; the factor covers the DC offset of the first asymmetrical cycle (√2 × 1.8).
  7. A generator on an infinite bus has H = 5 MJ/MVA, f = 50 Hz, P_m = 0.8 pu and P_max = 2.0 pu before and after a terminal three-phase fault. The critical clearing angle in degrees (nearest integer) is:

    Numerical answer — type the value.

    Show answer

    Answer: 89

    δ₀ = arcsin 0.4 = 23.58° = 0.4115 rad; cos δ_c = 0.4(π − 0.8230) − cos 23.58° = 0.0109, so δ_c = 89.4°.
  8. With the symmetrical-component operator a = 1∠120°, the magnitude of (1 + a) is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 1

    1 + a = 1 − 0.5 + j0.866 = 0.5 + j0.866 = 1∠60°, i.e. −a², because 1 + a + a² = 0. The tempting 2 adds the magnitudes as if the phasors were aligned.
  9. A perfectly balanced set of three-phase currents (equal magnitudes, 120 degrees apart, sequence abc) contains

    1. only positive-sequence components
    2. equal positive- and negative-sequence components
    3. all three sequence components equally
    4. only zero-sequence components
    Show answer

    Answer: A — only positive-sequence components

    For I_b = a²I_a and I_c = aI_a, the formulas give I₁ = I_a and I₂ = I₀ = 0 because 1 + a + a² = 0. Zero sequence, the tempting option, needs three equal in-phase currents.
  10. Which fault involves no zero-sequence current at all?

    1. double line-to-ground fault
    2. all of these carry zero-sequence current
    3. single line-to-ground fault
    4. line-to-line fault without ground
    Show answer

    Answer: D — line-to-line fault without ground

    With no path to earth, I_a + I_b + I_c = 0, so I₀ = 0 and only the positive and negative networks connect. The tempting double line-to-ground fault looks similar but has an earth path that carries 3I₀.
  11. SF₆ gas is widely used in high-voltage circuit breakers chiefly because it

    1. is cheaper than air
    2. is strongly electronegative and has high dielectric strength
    3. is a good electrical conductor that shorts the arc
    4. burns to produce a cooling flame
    Show answer

    Answer: B — is strongly electronegative and has high dielectric strength

    SF₆ captures free electrons, so the arc channel de-ionises rapidly at current zero and the gap recovers its strength, about 2 to 3 times that of air. Conducting the arc away, the tempting idea, would prevent interruption rather than aid it.
  12. A distance (impedance) relay decides whether a fault is inside its zone by measuring

    1. the current alone
    2. the ratio of voltage to current at the relay location
    3. the difference between currents at the two line ends
    4. the frequency of the system
    Show answer

    Answer: B — the ratio of voltage to current at the relay location

    V/I at the relay equals the line impedance up to the fault, which is proportional to distance, so the reach is fixed largely independent of source strength. The difference of end currents is the tempting differential (unit) principle.
  13. The inertia constant H of a synchronous machine is expressed in

    1. kg·m²
    2. per unit of torque
    3. MJ/MVA, which has the dimension of seconds
    4. MW/Hz
    Show answer

    Answer: C — MJ/MVA, which has the dimension of seconds

    H is the stored kinetic energy at synchronous speed divided by the MVA rating, MJ/MVA, i.e. seconds; typical values are 2 to 9 s. kg·m² is the tempting moment of inertia J, from which H is derived.
  14. Only phase a carries current, I_a = 10∠0° A, with I_b = I_c = 0. The magnitude of its positive-sequence component, in A to two decimal places, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 3.33

    I₁ = (I_a + aI_b + a²I_c)/3 = 10/3 = 3.33 A, and I₂ and I₀ are also 3.33 A each, which is why a single line-to-ground fault connects all three networks in series. The tempting 10 A forgets the factor 1/3.
  15. A generator with E = 1.0 pu, X₁ = X₂ = 0.25 pu and X₀ = 0.1 pu (solidly grounded) has a single line-to-ground fault through a fault reactance of j0.05 pu. The fault current, in pu, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 4

    I_f = 3E/(X₁ + X₂ + X₀ + 3X_f) = 3/(0.25 + 0.25 + 0.1 + 0.15) = 4 pu. The tempting 4.62 pu adds the fault reactance only once instead of 3X_f.
  16. At a circuit breaker the system inductance is 1.6 mH and the stray capacitance is 0.01 µF. The natural frequency of the restriking voltage transient, in kHz to one decimal place, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 39.8

    f_n = 1/(2π√(LC)) = 1/(2π√(1.6×10⁻¹¹)) = 39.8 kHz. The tempting 250 kHz is the angular frequency 1/√(LC) in krad/s.
  17. A generator with H = 4 MJ/MVA on a 50 Hz system suddenly has an accelerating power of 0.5 pu. Its initial rotor acceleration, in electrical rad/s² to two decimal places, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 19.63

    Swing equation: (H/πf) d²δ/dt² = P_a, so d²δ/dt² = πfP_a/H = 50π × 0.5/4 = 19.63 rad/s². The tempting 39.27 writes the swing equation as (H/ω_s) d²δ/dt² = P_a, dropping the 2 of 2H/ω_s.
  18. Which of the following statements about current-differential protection of a transformer or generator are correct?

    1. Ideally it stays stable for faults outside the zone (through faults)
    2. It operates on the difference between the currents entering and leaving the protected zone
    3. It is mainly used as back-up protection for faults on distant lines
    4. CT mismatch and saturation can cause false operation, which a percentage bias guards against
    Show answer

    Answer: A — Ideally it stays stable for faults outside the zone (through faults); B — It operates on the difference between the currents entering and leaving the protected zone; D — CT mismatch and saturation can cause false operation, which a percentage bias guards against

    Differential protection compares in and out currents, so a through fault gives no difference; biasing the restraint with the through current keeps CT errors from tripping it. The tempting fourth is false: it is unit protection with no reach outside its CTs, so it cannot back up remote lines.
  19. Phase currents are I_a = 10∠0° A, I_b = 10∠−120° A and I_c = 0 (phase c open). The magnitude of the positive-sequence current, in A to two decimal places, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 6.67

    aI_b = 10∠0°, so I₁ = (10 + 10 + 0)/3 = 6.67 A; the negative and zero sequences are each 3.33 A. The tempting 3.33 A applies a² to I_b, which builds the negative-sequence component instead.
  20. A generator on an infinite bus delivers P_m = 1.0 pu with P_max = 2.0 pu before and after a fault; during the fault P_max falls to 0.5 pu. The critical clearing angle, in degrees to one decimal place, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 92.7

    δ₀ = 30°, δ_max = 150°, and equal areas give cos δ_cr = [P_m(δ_max − δ₀) + P₃ cos δ_max − P₂ cos δ₀]/(P₃ − P₂) = −0.047, so δ_cr = 92.7 degrees; integrating the two areas numerically confirms the balance. The tempting 79.6 degrees treats the fault as a complete outage (P₂ = 0).
  21. A generator with E = 1.0 pu, X₁ = X₂ = 0.25 pu and X₀ = 0.1 pu (solidly grounded) has a bolted double line-to-ground fault on phases b and c. The magnitude of the phase b fault current, in pu to two decimal places, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 4.81

    I₁ = 1/j(0.25 + 0.25 || 0.1) = −j3.111, I₂ = j0.889, I₀ = j2.222, and I_b = I₀ + a²I₁ + aI₂ has magnitude 4.81 pu (I_a = 0 checks). The tempting 6.67 pu is the earth current 3|I₀|, not a phase current.