Power Systems II: Lines and Cables, Insulators, Compensation, Voltage and Frequency Control, Dispatch with Losses and the Swing Equation
Insulators: Voltage Across the String and String Efficiency
A suspension string of n discs is a series chain of capacitors C (each disc's self-capacitance) with shunt capacitances C′ to the earthed tower at each cap-and-pin junction. Those leakage capacitances draw current away, so the discs do not share the voltage equally: the disc nearest the conductor takes the highest voltage. For a 3-disc string with k = C′/C, numbering discs from the cross-arm, V₂ = V₁(1 + k) and V₃ = V₁(1 + 3k + k²), where V₃ is the unit nearest the line. String efficiency = (voltage across the whole string) / (n × voltage across the worst disc). With k = 0.2: V₁ : V₂ : V₃ = 1 : 1.20 : 1.64, the string voltage is 3.84 V₁, and the efficiency is 3.84/(3 × 1.64) = 78.0%; for k = 0.1 it improves to 86.8%. Efficiency is 100% only if k = 0, and falls as the string lengthens. Remedies: a longer cross-arm (smaller k), a guard (grading) ring that adds capacitance from the line end to the intermediate caps, and capacitance grading with larger-capacitance discs near the line. Wet-weather efficiency is higher because surface leakage tends to equalise the voltage.
| Item | Value | Meaning |
|---|---|---|
| String efficiency | V_string / (n · V_worst) | always below 100% |
| Worst disc | nearest the conductor | first to flash over, so it fixes the string rating |
| Grading ring | adds capacitance line-end → caps | equalises voltage, raises efficiency |

A suspension string of n discs is a series chain of capacitors C (each disc's self-capacitance) with shunt capacitances C′ to the earthed tower at each cap-and-pin junction. Those leakage…
Compensation, Voltage Control, Power-Factor Correction and Frequency Control
Voltage is governed mainly by reactive power: ΔV ≈ (P R + Q X)/V_r, and X ≫ R on transmission lines, so Q matters most. A feeder with R = 5 Ω, X = 10 Ω delivering 20 MW and 10 MVAr at 33 kV drops (20×5 + 10×10)/33 = 6.06 kV (18.4%); a 6 MVAr shunt capacitor at the load reduces it to 4.24 kV. Tools: tap-changing transformers, shunt capacitors (supply lagging VAr at heavy load), shunt reactors (absorb VAr at light load and Ferranti rise), synchronous condensers, SVCs. Series compensation places a capacitor in the line to cancel part of X: with degree of compensation K_c = X_c/X_L = 0.5, a 40 Ω line behaves as 20 Ω and its steady-state limit P_max = V_sV_r/X doubles (from V²/40 to V²/20), improving stability and reducing voltage drop, at the risk of sub-synchronous resonance. Power-factor correction: the capacitor needed is Q_c = P (tan φ₁ − tan φ₂); for 1000 kW from 0.8 to 0.95 lagging that is 1000 × (0.7500 − 0.3287) = 421.3 kVAr.
Frequency follows the balance of real power. When load rises, generators slow, and the governor with droop R (the per-unit speed change for a 1 pu power change) raises output: Δf = −R ΔP. A 5% droop unit loses 0.50 Hz of frequency when it picks up 20% of its rating. With several machines on the grid the frequency change is common and each takes ΔP_i = −Δf / R_i (in consistent units), so units share a load change in inverse proportion to their droop — here a 100 MW unit with 4% droop and a 200 MW unit with 5% take 23.1 and 36.9 MW of a 60 MW load rise. Load-frequency control (LFC) adds an integral action that restores nominal frequency and tie-line schedule using the area control error, ACE = ΔP_tie + B Δf, with B the frequency-bias. Swing equation: the rotor's acceleration obeys (2H/ω_s) d²δ/dt² = P_m − P_e (δ in electrical radians, H the inertia constant in MJ/MVA), so δ̈ = (180 f/H)(P_m − P_e) electrical degrees/s². For H = 5 s, f = 50 Hz and an accelerating power of 0.5 pu, δ̈ = 900°/s². The equal-area criterion integrates this to find the critical clearing angle.
- Generators slow
- Governors raise outputΔf = −R ΔP
- Units share the changeInversely to their droop
- LFC restores nominal frequencyIntegral action on ACE
Voltage is governed mainly by reactive power: ΔV ≈ (P R + Q X)/V_r, and X ≫ R on transmission lines, so Q matters most. A feeder with R = 5 Ω, X = 10 Ω delivering 20 MW and 10 MVAr at 33 kV…
Economic Dispatch with Losses and Per-Unit Bookkeeping
Lossless dispatch minimises ΣC_i(P_i) subject to ΣP_i = P_D; the Lagrange condition is equal incremental cost, dC_i/dP_i = λ for every unit not at a limit. For C₁ with IC₁ = 0.02 P₁ + 2 and C₂ with IC₂ = 0.03 P₂ + 2.5 ($/MWh) meeting 300 MW: 0.02 P₁ + 2 = 0.03 (300 − P₁) + 2.5 gives P₁ = 190 MW, P₂ = 110 MW and λ = 5.80 $/MWh. A unit at a limit is held there and drops out of the equal-λ rule. With transmission losses P_L, a megawatt from unit i costs more than its own incremental cost because it also raises losses: the condition becomes dC_i/dP_i × L_i = λ, with the penalty factor L_i = 1 / (1 − ∂P_L/∂P_i), and the loss is modelled by the B-coefficients, P_L = ΣΣ P_i B_ij P_j. If ∂P_L/∂P_i = 0.1, L_i = 1.111 and a unit whose own IC is 6 $/MWh is treated as costing 6.67: remote units, which waste more in the lines, are loaded less.
Per-unit quantities remove transformer ratios from the arithmetic: Z_pu = Z_ohm S_base / V_base². Changing base: Z_new = Z_old × (S_new/S_old) × (V_old/V_new)² — the voltage ratio is squared and in the opposite sense to the MVA ratio. A 0.2 pu reactance on 50 MVA, 11 kV becomes 0.2 × (100/50) × (11/11.5)² = 0.3660 pu on 100 MVA, 11.5 kV. A transformer's pu impedance is the same viewed from either side if the bases follow its turns ratio, which is why per-unit networks need no ideal transformers. The base MVA is common to the whole system; base voltages differ by the turns ratios.
Lossless dispatch minimises ΣC_i(P_i) subject to ΣP_i = P_D; the Lagrange condition is equal incremental cost, dC_i/dP_i = λ for every unit not at a limit. For C₁ with IC₁ = 0.02 P₁ + 2 and…
Key takeaways
- Line models: short A = D = 1, B = Z; nominal-π A = D = 1 + YZ/2, C = Y(1 + YZ/4); AD − BC = 1. Ferranti rise: an unloaded long line has V_r > V_s, cured by shunt reactors.
- Cables have 20–30 times the capacitance and low surge impedance, so charging current limits AC cable length; long cables use DC.
- String efficiency = V_string/(n·V_worst); the disc nearest the line is worst; for 3 discs V₂ = V₁(1+k), V₃ = V₁(1+3k+k²); grading rings and longer cross-arms help.
- Q controls voltage (ΔV ≈ (PR + QX)/V), P controls frequency (Δf = −RΔP); Q_c = P(tan φ₁ − tan φ₂); series compensation cuts X and raises the P_max = V²/X limit.
- Economic dispatch: equal incremental cost, with penalty factors L = 1/(1 − ∂P_L/∂P) when losses are counted; Z_new = Z_old (S_new/S_old)(V_old/V_new)²; swing equation δ̈ = (180f/H)(P_m − P_e).
Practice questions (24)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
The Ferranti effect is the rise of receiving-end voltage above sending-end voltage on:
Show answer
Answer: D — a lightly loaded or open-circuited long line
The line charging current, flowing through the series inductance, raises the voltage along the line when the load current is small. Shunt reactors absorb the excess reactive power.For a nominal-π medium line with series impedance Z and total shunt admittance Y, the A constant is:
Show answer
Answer: A — 1 + YZ/2
With half of Y at each end, A = D = 1 + YZ/2, B = Z and C = Y(1 + YZ/4), satisfying AD − BC = 1. The nominal-T gives A = 1 + YZ/2 too but B = Z(1 + YZ/4).Compared with an overhead line of the same rating, a cable has:
Show answer
Answer: A — much higher capacitance and lower surge impedance
Close conductor spacing and a high-permittivity dielectric make C about 20–30 times larger and L smaller, so Z_c = √(L/C) is low and the charging current is large, limiting AC cable length.
Show the other 21 questions
In a 3-disc suspension string, the ratio of shunt capacitance to self-capacitance is 0.2. The string efficiency is nearest to:
Show answer
Answer: B — 78.0%
With k = 0.2: V₂ = 1.2 V₁, V₃ = 1 + 0.6 + 0.04 = 1.64 V₁, total = 3.84 V₁, efficiency = 3.84/(3 × 1.64) = 0.7805.Which disc of a suspension insulator string has the highest voltage across it?
Show answer
Answer: A — the one nearest the conductor
The shunt capacitances to the tower draw current off at each junction, so the current through the discs (and the voltage across them) grows towards the line end.A load of 1000 kW at 0.8 power factor lagging is corrected to 0.95 lagging. Find the capacitor rating needed in kVAr (nearest integer).
Numerical answer — type the value.
Show answer
Answer: 421
Q_c = P (tan φ₁ − tan φ₂) = 1000 (0.75 − 0.3287) = 421.3 kVAr.A 40 Ω line is series-compensated by 50%. Its steady-state power-transfer limit V_sV_r/X becomes:
Show answer
Answer: D — twice the uncompensated value
The capacitor cancels half of X, leaving 20 Ω, so P_max = V_sV_r/X doubles. Stability margin improves, at the price of possible sub-synchronous resonance.Two generators with droops R₁ and R₂ (same per-unit basis, different ratings) share an increase of load. They share it:
Show answer
Answer: B — in inverse proportion to their droops (per MW basis)
The frequency change Δf is common; each unit changes output by ΔP_i = Δf/R_i (R_i in Hz per MW), so the unit with the smaller droop takes more. In per-unit on its own rating this makes equal-droop units share in proportion to rating.With transmission losses included, the economic-dispatch condition for unit i is:
Show answer
Answer: A — dC_i/dP_i × L_i = λ, where L_i = 1/(1 − ∂P_L/∂P_i)
The Lagrangian is ΣC_i + λ(P_D + P_L − ΣP_i), so dC_i/dP_i = λ(1 − ∂P_L/∂P_i), i.e. dC_i/dP_i × [1/(1 − ∂P_L/∂P_i)] = λ. Units that raise losses more are penalised more.Because of skin effect, the resistance of a transmission-line conductor at 50 Hz is
Show answer
Answer: D — slightly greater than its DC resistance
Alternating current crowds towards the surface, so the effective conducting area shrinks and R_ac exceeds R_dc, by a few per cent at power frequency. The tempting zero misreads surface crowding as a superconducting skin.An overhead conductor weighing 10 N/m is strung between level supports 200 m apart with a horizontal tension of 20 kN. Using the parabolic approximation, the sag, in m, is ____.
Numerical answer — type the value.
Show answer
Answer: 2.5
S = wL²/(8T) = 10 × 200²/(8 × 20 000) = 2.5 m. The tempting 10 m uses wL²/(2T), which is the formula with half the span length rather than the full span.A guard (grading) ring is fitted at the line end of a suspension insulator string to
Show answer
Answer: A — make the voltage across the discs more nearly equal
The ring adds capacitance from the line to each link pin, cancelling the charging current through the shunt capacitances so the disc voltages equalise and string efficiency rises. Mechanical strength is the tempting but unrelated role of the cap-and-pin hardware.Two identical units have incremental costs IC = 20 + 0.1P (Rs/MWh, P in MW) and together supply 200 MW, losses neglected. The economic output of unit 1, in MW, is ____.
Numerical answer — type the value.
Show answer
Answer: 100
Equal incremental cost with identical curves means equal outputs, 100 MW each, at λ = 30 Rs/MWh. The tempting 200 MW loads one unit fully, which raises its incremental cost above the other’s.A 100 MW generator has a governor speed droop of 5 per cent on a 50 Hz system. If the frequency falls by 0.5 Hz, the increase in its output, in MW, is ____.
Numerical answer — type the value.
Show answer
Answer: 20
ΔP/P_rated = (Δf/f)/R = (0.5/50)/0.05 = 0.2, i.e. 20 MW. The tempting 10 MW multiplies by the droop instead of dividing by it.Two units have incremental costs IC₁ = 20 + 0.2P₁ and IC₂ = 16 + 0.25P₂ (Rs/MWh, P in MW) and share a 300 MW load, losses neglected and limits not binding. The economic output of unit 1, in MW to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 157.8
Setting IC₁ = IC₂ = λ with P₁ + P₂ = 300 gives 9λ = 464, λ = 51.56 Rs/MWh, P₁ = 157.8 MW and P₂ = 142.2 MW. The tempting 150 MW splits the load equally, ignoring the different cost slopes.A two-disc suspension string has a ratio of shunt (pin-to-earth) capacitance to self-capacitance of 0.1. Its string efficiency, in per cent to two decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 95.45
KCL at the link gives V₂ = V₁(1 + m) = 1.1V₁, so η = (V₁ + V₂)/(2V₂) = 2.1/2.2 = 95.45 per cent. The tempting 90.9 per cent is V₁/V₂, the ratio of disc voltages rather than the string efficiency.A three-phase line has solid round conductors of radius 1 cm at the corners of an equilateral triangle of side 2 m. Using GMR = 0.7788r, its inductance per phase, in mH/km to two decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 1.11
L = 2×10⁻⁷ ln(D/GMR) = 2×10⁻⁷ ln(2/0.007788) = 2×10⁻⁷ × 5.548 = 1.11 mH/km. The tempting 1.06 mH/km uses r instead of GMR, ignoring the internal flux linkage.An isolated area has a regulation R = 0.05 pu and a load-damping constant D = 1 pu on its own base. A sudden load increase of 0.01 pu occurs with no supplementary control. The steady-state frequency change on a 50 Hz base, in Hz to four decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: -0.0238
Δf = −ΔP_L/(D + 1/R) = −0.01/21 pu = −0.000476 × 50 = −0.0238 Hz. The tempting −0.025 Hz ignores the load damping D and uses 1/R alone.Compared with a single conductor of the same total cross-section, a bundled-conductor line
Show answer
Answer: A — has lower series inductive reactance; B — has a higher surge impedance loading; C — has lower corona loss
The larger GMR of a bundle lowers inductance and raises capacitance, so Z_c = √(L/C) falls and SIL = V²/Z_c rises, while the surface gradient and corona fall. Higher inductance, the tempting fourth, is the reverse of what bundling does.A unit has incremental cost IC = 20 + 0.1P (Rs/MWh, P in MW) and an incremental transmission loss ∂P_L/∂P = 0.2 at its bus. If the system λ is 40 Rs/MWh, its economic output, in MW, is ____.
Numerical answer — type the value.
Show answer
Answer: 120
The penalty factor is L = 1/(1 − 0.2) = 1.25, and L × IC = λ gives IC = 32, so P = (32 − 20)/0.1 = 120 MW. The tempting 200 MW sets IC = λ, ignoring the losses that the unit’s output causes.A three-disc suspension string carries 33 kV (to earth) and has a ratio of shunt to self-capacitance of 0.1. The voltage across the disc nearest the line conductor, in kV to two decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 12.68
With V₁ = 1: V₂ = 1.1 and V₃ = V₂ + m(V₁ + V₂) = 1.31, total 3.41, so V₃ = 33 × 1.31/3.41 = 12.68 kV. The tempting 11 kV assumes an equal share, which only a perfect guard ring would give.For the same line (conductor radius 1 cm, equilateral spacing 2 m, ε₀ = 8.854 x 10^(-12) F/m), the capacitance to neutral per phase, in µF/km to four decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 0.0105
C = 2πε₀/ln(D/r) = 5.563×10⁻¹¹/ln 200 = 1.050×10⁻¹¹ F/m = 0.0105 µF/km; capacitance uses the physical radius, not the GMR. The tempting 0.0100 µF/km uses GMR = 0.7788r, which belongs only to the inductance formula.Two generators on a 50 Hz system, rated 200 MW with 4 per cent droop and 300 MW with 5 per cent droop, share a sudden 50 MW load increase with no supplementary control and no load damping. The extra output of the 200 MW unit, in MW to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 22.7
Stiffness: 200/(0.04 × 50) = 100 MW/Hz and 300/(0.05 × 50) = 120 MW/Hz, so Δf = 50/220 = 0.227 Hz and unit 1 picks up 22.7 MW. The tempting 20 MW shares the load in proportion to ratings, which holds only for equal per-unit droops.A line has A = 0.95∠1° and B = 0.5∠85° ohm-pu, with |V_s| = |V_r| = 1.0 pu. The maximum real power that can be received, in pu to two decimal places, is ____.
Numerical answer — type the value.
Show answer
Answer: 1.8
P_r,max = |V_s||V_r|/|B| − |A||V_r|² cos(β − α)/|B| = 2 − 1.9 cos 84° = 2 − 0.199 = 1.80 pu, reached at δ = β = 85 degrees. The tempting 2.00 pu is the lossless-line limit V²/X, which ignores the resistive term.