Control Systems at Working Depth: Time-Domain Specifications, Routh and Root Locus, Bode Margins, Lead–Lag and PID Design, State Space, Time Delay and Final Elements

Section 5 of the IN paper asks for transient response, steady-state error, Bode plots, phase and gain margins, Routh and Nyquist criteria, root loci, state-space representation, time-delay systems, actuators (control valves, servo valves, servo and stepper motors), P, PI, PID, cascade, feed-forward and ratio controllers, PID tuning and the design of lead, lag and lead–lag compensators — and the first chapter gave the section one chapter of statements, with no specification worked and no compensator designed. For the unity-feedback loop G = K/[s(s + 2)], K = 4 gives ζ = 0.50, overshoot 16.3% and a ramp error of 1/K_v = 0.5, while K = 25 gives ζ = 0.20 and 52.7% overshoot. The polynomial s⁴ + 2s³ + 3s² + 4s + 5 has 2 right-half-plane roots; K/[s(s + 2)(s + 4)] goes unstable at K = 48. A lead compensator for 45° of phase has α = 0.1716; Ziegler–Nichols with K_u = 8 and P_u = 2 s gives a PID of K_p = 4.8, T_i = 1 s, T_d = 0.25 s; and a 45° phase margin at 2 rad/s tolerates a delay of 0.393 s.
Overview

Second-Order Specifications and Steady-State Error

1 min read

The unity-feedback loop with G(s) = K/[s(s + 2)] has the closed-loop denominator s² + 2s + K, so ω_n = √K and ζ = 1/√K. Specifications: percentage overshoot M_p = 100 exp(−πζ/√(1 − ζ²)); peak time t_p = π/(ω_n√(1 − ζ²)); 2% settling time t_s ≈ 4/(ζω_n); rise time t_r ≈ (1.8)/ω_n for ζ ≈ 0.5; all of them set by the pole position −ζω_n ± jω_n√(1 − ζ²). For K = 4: ω_n = 2, ζ = 0.50, M_p = 16.3%, t_p = 1.81 s, t_s = 4.0 s. For K = 25: ω_n = 5, ζ = 0.20, M_p = 52.7%, t_p = 0.64 s — a larger gain makes the loop faster but more oscillatory, while t_s stays at 4 s because Re(pole) = −1 is unchanged. Steady-state error depends on the type (number of integrators in G): e_ss = 1/(1 + K_p) for a step (finite only for type 0), 1/K_v for a ramp (type 1), 1/K_a for a parabola (type 2), with K_p = lim G(s), K_v = lim sG(s), K_a = lim s²G(s). Here type 1: K_v = K/2, so the ramp error is 1/K_v = 2/K = 0.5 for K = 4 and 0.08 for K = 25 (step error 0). A disturbance error is reduced by gain ahead of the disturbance entry point and by integral action there.

System typeStep e_ssRamp e_ssParabola e_ss
01/(1 + K_p)∞∞
101/K_v∞
2001/K_a

The unity-feedback loop with G(s) = K/[s(s + 2)] has the closed-loop denominator s² + 2s + K, so ω_n = √K and ζ = 1/√K. Specifications: percentage overshoot M_p = 100 exp(−πζ/√(1 − ζ²))…

Routh, Root Locus and Bode Margins

2 min read · 2 parts

Routh–Hurwitz: form the array from the characteristic polynomial; the number of sign changes in the first column equals the number of right-half-plane roots. For s⁴ + 2s³ + 3s² + 4s + 5 the first column is 1, 2, 1, −6, 5: two sign changes, 2 RHP roots (confirmed: 0.29 ± 1.42j). For the gain range of s³ + 6s² + 11s + K, the s¹ row is (66 − K)/6, so the loop is stable for 0 < K < 66 and oscillates at K = 66 at ω = √11 = 3.32 rad/s (the s² row 6s² + 66 = 0). A zero in the first column signals a root on the axis; a whole row of zeros means a symmetric root pair, solved from the auxiliary polynomial. Root locus (roots of 1 + KG = 0 as K goes 0 → ∞): for G = K/[s(s + 2)(s + 4)] there are 3 branches starting at 0, −2, −4 and ending at infinity along asymptotes at ±60° and 180° from the centroid σ = (0 − 2 − 4)/3 = −2; the breakaway point solves dK/ds = 0, 3s² + 12s + 8 = 0 → s = -0.845 (the other root, -3.155, is not on the locus); the locus crosses the imaginary axis at ω = √8 = 2.828 rad/s with K = 48 (the Routh limit of s³ + 6s² + 8s + K). Add a pole and the locus bends right; add a zero and it bends left (stabilising).

Bode margins. For L(s) = 20/[s(1 + 0.1s)(1 + 0.01s)] the magnitude crosses 0 dB at the gain-crossover frequency ω_gc = 12.44 rad/s, where the phase is −90° − arctan(0.1ω) − arctan(0.01ω), so the phase margin PM = 180° + ∠L(jω_gc) = 31.7°. The phase reaches −180° at the phase-crossover frequency ω_pc = 31.6 rad/s, where |L| = 0.1818, so the gain margin GM = −20 log|L(jω_pc)| = 14.8 dB. Both must be positive for stability of a minimum-phase loop; the rule of thumb is PM 30–60° and GM > 6 dB, and PM ≈ 100ζ degrees (for ζ < 0.6). A Nyquist plot says the same: N = Z − P encirclements of −1 count unstable closed-loop poles Z given P open-loop RHP poles (stable iff N = −P). Gain margin is the factor by which K can rise before instability: 10^(GM/20) = 5.50 here, so the same loop with K = 20 × 5.5 = 110 would sit on the stability boundary.

MethodAnswersExample result
Routh arrayRHP root count, K range0 < K < 66 for s³ + 6s² + 11s + K
Root locusPole paths against KBreakaway −0.845; K = 48 at ±j2.83
Bode marginsPM, GM from open loopPM 32°, GM 15 dB

Routh–Hurwitz: form the array from the characteristic polynomial; the number of sign changes in the first column equals the number of right-half-plane roots. For s⁴ + 2s³ + 3s² + 4s + 5 the…

Lead, Lag and PID Compensators and Ziegler–Nichols Tuning

2 min read · 2 parts

A lead compensator G_c = (1 + αTs)/(1 + Ts) (α < 1) adds a maximum phase φ_m = arcsin[(1 − α)/(1 + α)] at ω_m = 1/(T√α), and raises the gain at ω_m by 1/√α. For φ_m = 45°: α = (1 − sin 45°)/(1 + sin 45°) = 0.1716 and the gain boost is 2.414 (7.7 dB) — a single lead stage should supply no more than about 60° (α ≈ 0.07), beyond which two stages are cascaded. Design: find the phase deficit at the wanted crossover, add 5–10° margin, choose α, place ω_m at the new crossover, and set the gain so that |G_cG| = 1 there. Example: 30° needed at ω_m = 5 rad/s gives α = 0.3333 and T = 1/(5√α) = 0.3464 s, G_c = (1 + 0.1155s)/(1 + 0.3464s) with a compensating gain 1/√α = 1.73. Lead speeds the response, raises bandwidth and phase margin but amplifies noise. A lag compensator (1 + Ts)/(1 + βTs), β > 1, lowers high-frequency gain by β (so the crossover moves down where the phase is better) and raises low-frequency gain — it improves K_v and steady-state accuracy at the cost of speed; its corner is kept a decade below the crossover. Lead–lag does both.

PID controller u = K_p[e + (1/T_i)∫e dt + T_d de/dt]: P gives proportional correction (leaves an offset in a type-0 plant); I removes the offset but adds lag and can cause windup (hence anti-windup); D anticipates and adds damping but amplifies noise (hence a filter on D and derivative on measurement). Ziegler–Nichols closed-loop tuning: raise K_p on a P-only loop until sustained oscillation — ultimate gain K_u and ultimate period P_u. For K_u = 8, P_u = 2 s: P K_p = 0.5K_u = 4; PI K_p = 0.45K_u = 3.6, T_i = P_u/1.2 = 1.667 s; PID K_p = 0.6K_u = 4.8, T_i = P_u/2 = 1 s, T_d = P_u/8 = 0.25 s. These give a quarter-amplitude decay, which is aggressive; the open-loop (process reaction curve) variant reads delay L and time constant τ from a step test and sets K_p = 1.2τ/(KL) for PID. Cascade control puts a fast inner loop (valve position, flow) inside a slow outer one so disturbances are corrected before reaching the outer variable; feed-forward acts on a measured disturbance before it shows up as error; ratio control holds one flow in fixed proportion to another (air to fuel).

CompensatorTransfer functionEffect
Lead(1 + αTs)/(1 + Ts), α < 1+ phase near ω_m, faster, noisier
Lag(1 + Ts)/(1 + βTs), β > 1+ low-frequency gain, better K_v, slower
PIK_p(1 + 1/T_is)Removes offset
PIDK_p(1 + 1/T_is + T_ds)Offset removed and damping added
Designing a lead compensator
  1. Find the phase deficitAt the wanted crossover
  2. Add 5–10° margin
  3. Choose αφ_m = arcsin[(1 − α)/(1 + α)]
  4. Place ω_m at the new crossover
  5. Set gain so |G_cG| = 1 there

A lead compensator G_c = (1 + αTs)/(1 + Ts) (α < 1) adds a maximum phase φ_m = arcsin[(1 − α)/(1 + α)] at ω_m = 1/(T√α), and raises the gain at ω_m by 1/√α. For φ_m = 45°: α = (1 − sin…

State Space, Time Delay and Final Control Elements

3 min read · 3 parts

State space: ẋ = Ax + Bu, y = Cx + Du. The transfer function is G(s) = C(sI − A)⁻¹B + D, and its poles are the eigenvalues of A. For A = [[0, 1], [−2, −3]], B = [0, 1]ᵀ, C = [1, 0]: det(sI − A) = s² + 3s + 2 → poles −1 and −2, G(s) = 1/(s² + 3s + 2). Controllability needs rank[B, AB, …, Aⁿ⁻¹B] = n (here [B, AB] = [[0, 1], [1, −3]], rank 2, so controllable); observability needs rank[C; CA; …] = n. With full-state feedback u = −Kx the closed-loop matrix is A − BK; to place the poles at −3 and −4 for the example, s² + (3 + k₂)s + (2 + k₁) = s² + 7s + 12 gives k₁ = 10, k₂ = 4. A time delay e^(−sT) has unit gain and phase −ωT rad: it adds lag without reducing gain, so it eats phase margin; the delay margin DM = PM(rad)/ω_gc — for PM = 45° and ω_gc = 2 rad/s, DM = 0.393 s — is the extra delay the loop tolerates. A Padé approximation e^(−sT) ≈ (1 − sT/2)/(1 + sT/2) turns it into a rational function (with a right-half-plane zero, giving the inverse response seen in some processes). The Smith predictor removes the delay from the loop dynamics (not from the output).

Final control elements. A control valve passes Q = C_v√(ΔP/SG) (gpm, psi) and has an inherent characteristic relating flow to stem lift x: linear Q/Q_max = x; equal-percentage Q/Q_max = R^(x − 1) with rangeability R ≈ 50 (at 50% lift only 14% of the flow, then a constant % change in flow per unit lift — the gain that stays nearly constant once the system pressure drop is installed); quick-opening for on-off service. Choose fail-open or fail-close for the safe state. A servo valve (torque motor + flapper-nozzle + spool) positions hydraulic flow at high bandwidth. A DC servo motor is, to first order, ω/V = K_m/(τ_ms + 1) with the mechanical time constant τ_m = RJ/(K_tK_b + RB); an AC servo adds a two-phase winding. A stepper motor moves one fixed step per pulse, open loop: a 1.8° step gives 360/1.8 = 200 steps per revolution, so 1000 pulses/s turn it at 1000/200 = 5 rev/s = 300 rpm; 16× microstepping gives 3200 steps/rev; torque falls with step rate and a stalled step is lost silently, so position feedback is needed for safety-critical motion. Supervisory control, DCS and PLC: a DCS coordinates many continuous loops across a plant with set-point hierarchy; a PLC executes discrete sequence logic (ladder) in a scan cycle; supervisory control sets set-points and optimises, not closing the fast loops.

ElementKey figure
Equal-percentage valve, R = 5014% of full flow at 50% lift
Stepper, 1.8° step200 steps/rev; 1000 pulses/s = 300 rpm
DC servo motorFirst-order: K_m/(τ_ms + 1)
Delay marginPM/ω_gc = 0.393 s for 45° at 2 rad/s
🎯 Second-order specifications, computed
For a second-order system with ω_n = 10 rad/s and ζ = 0.5, the peak overshoot is exp(−πζ/√(1 − ζ²)) = 16.3%, the peak time is π/(ω_n√(1 − ζ²)) = 0.363 s and the 2% settling time is about 4/(ζω_n) = 0.8 s. Increasing ζ reduces overshoot but slows the rise, and the dominant closed-loop poles at −ζω_n ± jω_n√(1 − ζ²) = −5 ± j8.66 fix all three. A phase margin near 60° corresponds roughly to ζ = 0.6, a rule of thumb PM ≈ 100ζ degrees for ζ below about 0.6.

State space: ẋ = Ax + Bu, y = Cx + Du. The transfer function is G(s) = C(sI − A)⁻¹B + D, and its poles are the eigenvalues of A. For A = [[0, 1], [−2, −3]], B = [0, 1]ᵀ, C = [1, 0]: det(sI…

Key takeaways

  • Second order: ω_n = √K, ζ = 1/√K for K/[s(s + 2)]; M_p = 100 exp(−πζ/√(1 − ζ²)), t_s ≈ 4/(ζω_n); ramp error 1/K_v for type 1.
  • Routh: sign changes in the first column count RHP roots; for s³ + 6s² + 11s + K stability needs K < 66. Root-locus asymptote centroid, breakaway from dK/ds = 0, axis crossing from Routh.
  • Bode: PM = 180° + ∠L at gain crossover, GM = −20 log|L| at phase crossover; both positive for stability; delay margin = PM(rad)/ω_gc.
  • Lead α = (1 − sin φ_m)/(1 + sin φ_m), ω_m = 1/(T√α); lag raises low-frequency gain; Ziegler–Nichols PID: K_p = 0.6K_u, T_i = P_u/2, T_d = P_u/8.
  • State space: poles are eigenvalues of A; controllability rank [B AB…]; state feedback places poles; valves are linear, equal-percentage or quick-opening; a 1.8° stepper has 200 steps/rev.

Practice questions (24)

Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.

  1. A unity-feedback loop has G(s) = K/[s(s + 2)] with K = 4. The percentage overshoot of its step response (one decimal) is:

    Numerical answer — type the value.

    Show answer

    Answer: 16.3

    ω_n = 2, ζ = 1/√4 = 0.5; M_p = 100 exp(−π × 0.5/√0.75) = 16.3%.
  2. For the same loop with K = 4 the steady-state error to a unit-ramp input is:

    1. 0.5
    2. 0.25
    3. 2
    4. 0
    Show answer

    Answer: A — 0.5

    The loop is type 1, K_v = lim sG(s) = K/2 = 2, so e_ss = 1/K_v = 0.5. A step would give zero error; a parabola, infinity.
  3. The polynomial s³ + 6s² + 11s + K has all roots in the left half-plane for:

    1. 0 < K < 11
    2. K > 66
    3. 0 < K < 66
    4. K < 6
    Show answer

    Answer: C — 0 < K < 66

    The s¹ row of the Routh array is (6 × 11 − K)/6, positive only if K < 66, and the last row needs K > 0. At K = 66 the roots on the axis are ±j√11.
Show the other 21 questions
  1. For the root locus of G(s) = K/[s(s + 2)(s + 4)], the gain K at which the locus crosses the imaginary axis is:

    Numerical answer — type the value.

    Show answer

    Answer: 48

    The characteristic polynomial is s³ + 6s² + 8s + K; Routh gives (48 − K)/6 in the s¹ row, so K = 48 and ω = √8 = 2.83 rad/s.
  2. For the loop L(s) = 20/[s(1 + 0.1s)(1 + 0.01s)], the system is stable with:

    1. a negative phase margin
    2. a gain margin of 0 dB
    3. no gain crossover
    4. a phase margin of about 32° and a gain margin of about 15 dB
    Show answer

    Answer: D — a phase margin of about 32° and a gain margin of about 15 dB

    ω_gc = 12.4 rad/s with PM = 32°, and ω_pc = 31.6 rad/s with GM = 14.8 dB; both are positive so the closed loop is stable.
  3. A lead compensator is to supply a maximum phase lead of 45°. The value of α in (1 + αTs)/(1 + Ts) is (four decimals):

    Numerical answer — type the value.

    Show answer

    Answer: 0.1716

    α = (1 − sin 45°)/(1 + sin 45°) = 0.2929/1.7071 = 0.1716; the gain at ω_m rises by 1/√α = 2.414 (7.7 dB).
  4. A P-only loop oscillates steadily at K_u = 8 with period P_u = 2 s. The Ziegler–Nichols PID setting for the derivative time T_d in seconds is (two decimals):

    Numerical answer — type the value.

    Show answer

    Answer: 0.25

    Ziegler–Nichols PID: K_p = 0.6K_u = 4.8, T_i = P_u/2 = 1 s, T_d = P_u/8 = 0.25 s.
  5. A system has A = [[0, 1], [−2, −3]]. Its poles are:

    1. −1 and −2
    2. 0 and −3
    3. 1 and 2
    4. −2 and −3
    Show answer

    Answer: A — −1 and −2

    The poles are the eigenvalues of A: det(sI − A) = s² + 3s + 2 = (s + 1)(s + 2). The matrix entries themselves are not the poles.
  6. A loop has a phase margin of 45° at a gain-crossover frequency of 2 rad/s. The delay margin in seconds (three decimals) is:

    Numerical answer — type the value.

    Show answer

    Answer: 0.393

    DM = PM(rad)/ω_gc = 0.7854/2 = 0.393 s; any extra delay beyond that drives the phase margin negative.
  7. Which statements about final control elements are correct?

    1. A 1.8° stepper motor has 200 steps per revolution
    2. An equal-percentage valve passes only about 14% of full flow at 50% lift when R = 50
    3. A servo valve has a lower bandwidth than a solenoid on-off valve
    4. A stepper motor in open loop can lose steps without any indication
    Show answer

    Answer: A — A 1.8° stepper motor has 200 steps per revolution; B — An equal-percentage valve passes only about 14% of full flow at 50% lift when R = 50; D — A stepper motor in open loop can lose steps without any indication

    Servo valves exist for high bandwidth proportional hydraulic positioning; an on-off solenoid valve has no continuous response at all.
  8. A second-order system has ω_n = 10 rad/s and ζ = 0.5. Its 2 % settling time, using t_s ≈ 4/(ζω_n), in s, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 0.8

    t_s = 4/(ζω_n) = 4/5 = 0.8 s. Using 4/ω_n = 0.4 s ignores damping; the envelope decays as e^(−ζω_n t), so ζ belongs in the denominator.
  9. A unity-feedback system has G(s) = 4/(s + 2). Its steady-state error to a unit step (three decimals) is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 0.333

    K_p = G(0) = 2, so e_ss = 1/(1 + K_p) = 1/3 = 0.333. Writing 1/K_p = 0.5 uses the ramp-error form; a type-0 loop always leaves this finite step offset.
  10. On a Bode plot, a pole at the origin (1/s) contributes

    1. a +20 dB/decade line and +90° phase
    2. a −40 dB/decade line and −180° phase
    3. a −20 dB/decade magnitude line at all frequencies and a constant −90° phase
    4. a flat magnitude and −45° phase
    Show answer

    Answer: C — a −20 dB/decade magnitude line at all frequencies and a constant −90° phase

    |1/(jω)| = 1/ω falls 20 dB per decade through 0 dB at ω = 1, and its angle is fixed at −90°. The +20 dB/decade, +90° option describes a zero at the origin; −45° is the phase of a real pole only at its corner.
  11. The PID controller term that most strongly amplifies high-frequency measurement noise is the

    1. derivative term
    2. integral term
    3. proportional term
    4. set-point weighting
    Show answer

    Answer: A — derivative term

    The derivative gain grows as ω (K_d s), so fast noise is magnified; practical controllers add a filter on that term. The integral term does the opposite, attenuating high frequencies as 1/ω.
  12. A first-order system has ẋ = −2x + u and y = 3x. Its dc gain y/u is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 1.5

    G(s) = C(sI − A)⁻¹B = 3/(s + 2), so G(0) = 1.5. Answering 3 takes only the output gain C and forgets that the state settles at x = u/2.
  13. A control valve with an equal-percentage characteristic gives

    1. flow directly proportional to stem travel
    2. nearly full flow within the first small opening
    3. equal fractional changes in flow for equal increments of stem travel
    4. constant flow regardless of opening
    Show answer

    Answer: C — equal fractional changes in flow for equal increments of stem travel

    Equal percentage means dQ/Q ∝ dx, an exponential curve; each step of travel changes the flow by the same percentage of its current value. Proportional flow is the linear trim, and "nearly full flow early" is quick-opening.
  14. An underdamped second-order step response shows a 25 % peak overshoot. The damping ratio ζ (three decimals) is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 0.404

    ζ = −ln(M_p)/√(π² + ln²M_p) = 1.386/√(9.870 + 1.922) = 0.404. Inverting with M_p = 0.25 as a percentage-free number is essential; using ln 25 instead gives a meaningless ζ above 1.
  15. For the root locus of G(s)H(s) = K/[s(s + 2)(s + 4)], the asymptotes meet the real axis at σ = ____.

    Numerical answer — type the value.

    Show answer

    Answer: -2

    σ = (Σ poles − Σ zeros)/(n − m) = (0 − 2 − 4)/3 = −2, with asymptotes at ±60° and 180°. Dividing by 2 instead of the pole–zero excess 3 gives −3.
  16. A P-only test gives ultimate gain K_u = 10 and ultimate period P_u = 3 s. The Ziegler–Nichols PI setting for the integral time T_i, in s, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 2.5

    Z–N closed-loop PI: K_c = 0.45K_u = 4.5 and T_i = P_u/1.2 = 2.5 s. The PID rule T_i = P_u/2 = 1.5 s is the tempting mix-up between the two tuning rows.
  17. For A = [[0, 1], [0, 0]] (a double integrator), the (1, 2) entry of the state-transition matrix e^(At) at t = 3 s is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 3

    A is nilpotent (A² = 0), so e^(At) = I + At = [[1, t], [0, 1]] and the (1, 2) entry is t = 3. Answering e³ ≈ 20.1 exponentiates the entries one by one, which is not how a matrix exponential works.
  18. A liquid control valve (specific gravity 1) has C_v = 10 and a pressure drop of 16 psi. Using Q = C_v√(ΔP/G), the flow in US gpm is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 40

    Q = 10 × √16 = 40 gpm. Forgetting the square root gives 160 gpm; flow through a restriction grows only with the square root of the pressure drop.
  19. For the root locus of G(s)H(s) = K/[s(s + 2)(s + 4)], the break-away point on the real axis between 0 and −2 is s = ____ (three decimals).

    Numerical answer — type the value.

    Show answer

    Answer: -0.845

    K = −s(s + 2)(s + 4) = −(s³ + 6s² + 8s); dK/ds = 0 gives 3s² + 12s + 8 = 0, s = −0.845 or −3.155. Only -0.845 lies on a locus segment (between 0 and −2); −3.155 is on a non-locus stretch, so it is the tempting wrong root.
  20. A lead compensator (1 + αTs)/(1 + Ts) has α = 4 and T = 0.1 s. The maximum phase lead it supplies, in degrees (two decimals), is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 36.87

    sin φ_m = (α − 1)/(α + 1) = 3/5, so φ_m = 36.87°, occurring at ω_m = 1/(T√α) = 5 rad/s. Using tan φ_m = 3/5 gives 30.96°, the wrong inverse function.
  21. For an underdamped second-order system with fixed ω_n, the damping ratio is raised from 0.2 to 0.6. Which statements are correct?

    1. The 2 % settling time decreases.
    2. The rise time decreases.
    3. The peak overshoot decreases.
    4. The peak time increases.
    Show answer

    Answer: A — The 2 % settling time decreases.; C — The peak overshoot decreases.; D — The peak time increases.

    Overshoot e^(−ζπ/√(1−ζ²)) falls, ω_d = ω_n√(1−ζ²) falls so t_p = π/ω_d grows, and t_s ≈ 4/(ζω_n) shrinks. Rise time INCREASES with ζ because the response becomes more sluggish, so the last statement is the trap.