Power Electronics II: Three-Phase Bridges, Source Inductance, Line-Current Harmonics, Power and Distortion Factor, and Bidirectional Converters
Thyristor Converters: Firing Angle, Inversion and Source Inductance
Replace the diodes by thyristors fired at angle α after the natural-commutation instant: in continuous conduction V_dc = (3√2/π) V_LL cos α (three-phase fully controlled bridge) and V_dc = (2V_m/π) cos α (single-phase). For V_LL = 400 V: α = 30° gives 467.8 V, α = 60° gives 270.1 V, α = 90° gives 0.0 V; for α > 90° the mean voltage is negative and, if the load has a source of the right polarity (a DC machine regenerating, a battery), power flows from DC to AC — inverter operation, limited by the turn-off time to α below about 150–165° to avoid commutation failure. These are line-commutated (voltage-commutated) converters: the AC line's voltage turns the outgoing thyristor off. Current-commutated thyristor circuits (current-source inverters with capacitors) make the load current switch the devices. Half-controlled bridges (with a free-wheeling diode) cannot invert and have V_dc ∝ (1 + cos α), but a better input power factor at large firing angles.
Source inductance and overlap. The supply has inductance, so current cannot jump from the outgoing to the incoming thyristor: both conduct together for the overlap angle μ, during which the output is the average of the two phases. The result is a voltage drop ΔV = (3 X_s/π) I_d for the three-phase bridge (X_s = ωL_s per phase) — it looks like a resistance 3X_s/π that dissipates nothing — and the overlap satisfies cos α − cos(α + μ) = 2 X_s I_d / (√2 V_LL). With V_LL = 400 V, X_s = 0.2 Ω, I_d = 50 A, α = 30°: ΔV = 9.55 V, V_dc = 467.8 − 9.55 = 458.3 V, cos(α + μ) = 0.8660 − 0.0354 = 0.8307, so μ = 3.8°. Overlap grows with load current and with source reactance, reduces the output voltage, and in an inverter shortens the margin angle (γ = 180° − α − μ must stay above the turn-off angle).
- α = 30°467.8 V
- α = 60°270.1 V
- α = 90°0 V
- α > 90°: negativeInverter; α below about 150–165°
Replace the diodes by thyristors fired at angle α after the natural-commutation instant: in continuous conduction V_dc = (3√2/π) V_LL cos α (three-phase fully controlled bridge) and V_dc =…
Line-Current Harmonics, Distortion Factor and Power Factor
With large load inductance the three-phase bridge draws the quasi-square current above. Fourier analysis (done numerically here and confirmed against the closed form) gives no triplen or even harmonics and harmonics only at n = 6k ± 1 (5, 7, 11, 13, …) of amplitude I_n = I₁/n, with I₁ = (√6/π) I_d. For I_d = 100 A the fundamental is 78.0 A and the 5th, 7th, 11th and 13th are 15.6, 11.1, 7.1, 6.0 A. A thyristor converter delays the whole waveform by α, so the fundamental lags the supply voltage by α and the n-th harmonic by nα. The three-phase converter has THD = √(π²/9 − 1) = 31.1%; the single-phase bridge, whose current is a ±I_d square wave with odd harmonics n = 3, 5, 7…, I_n = I₁/n and I₁ = (2√2/π) I_d = 0.9 I_d, has THD = 48.3%. Where converters share a bus, the harmonics of different phase shifts partly cancel: a 12-pulse arrangement (two bridges fed 30° apart, with a Δ/Y transformer pair) removes the 5th and 7th and leaves 11, 13, 23, 25….
Power factor = distortion factor × displacement factor. With a sinusoidal voltage only the fundamental current carries real power, P = V I₁ cos φ₁, so PF = P/(V I_rms) = (I₁/I_rms) × cos φ₁. The distortion factor DF = I₁/I_rms is 0.9550 (= 3/π) for the three-phase bridge and 0.9003 (= 2√2/π) for the single-phase one — fixed by the waveshape, independent of α. The displacement factor cos φ₁ = cos α for a controlled converter. So PF = 0.955 cos α for the three-phase bridge: 0.955 at α = 0, 0.827 at 30°, 0.477 at 60° — a firing delay costs power factor linearly in cos α, which is the main drawback of phase control. Also THD = √(1/DF² − 1), the relation used above. With source overlap the displacement factor falls slightly below cos α. Improving it needs forced commutation (the converters below) or reactive compensation.
- Distortion factor DF = I₁/I_rms0.9550 three-phase, 0.9003 single-phase; fixed by waveshape
- Displacement factor cos φ₁ = cos αThree-phase PF: 0.955, 0.827, 0.477 at 0°, 30°, 60°
With large load inductance the three-phase bridge draws the quasi-square current above. Fourier analysis (done numerically here and confirmed against the closed form) gives no triplen or…
Bidirectional Converters: Dual Converters and the AC-to-DC Voltage-Source Converter
A DC drive needs torque and speed of either sign — four quadrants. One thyristor bridge can give V_dc of either sign but I_d of one sign only (thyristors conduct one way), so two bridges are connected anti-parallel as a dual converter: the forward bridge for I_d > 0 and the reverse bridge for I_d < 0. With circulating current the two bridges conduct together with firing angles α₁ + α₂ = 180° so their mean voltages are equal and opposite; an inter-group reactor limits the circulating ripple current, the response is fast and the changeover smooth, at the cost of larger rating and losses. Non-circulating operation fires only the bridge that carries the load, with a dead time of a few milliseconds at reversal, needing a current sensor and a logic circuit. The four quadrants of a DC machine: forward motoring (V > 0, I > 0), forward regeneration (V > 0, I < 0), reverse motoring (V < 0, I < 0) and reverse regeneration (V < 0, I > 0).
Bidirectional AC-to-DC voltage-source converter (the PWM rectifier, or active front end): a three-phase bridge of IGBTs with anti-parallel diodes, an inductor in each line and a DC-link capacitor, switched by sinusoidal PWM. It is a boost converter, so the DC voltage must exceed the peak line voltage: for 400 V line, V_dc ≥ √2 V_LL = 565.7 V (a practical link is 10–20% higher). Controlling the phase angle δ of the converter's terminal voltage V_c against the supply V_s sets the power through the line reactance X: P = 3 V_s V_c sin δ / X per phase quantities, and the quadrature part sets reactive power, so the current can be made sinusoidal and at unity power factor (or leading), with power flowing either way — rectifying for δ > 0, regenerating (inverting) for δ < 0. With V_s = 230 V, V_c = 235 V and X = 1 Ω, 10 kW needs δ = 3.54°. Compared with the thyristor bridge it gives low harmonics, controllable power factor and four-quadrant flow with a fixed DC voltage, at higher cost — the reason regenerative drives and grid-connected converters use it.
- Both bridges conduct; α₁ + α₂ = 180°
- Inter-group reactor
- Fast, smooth; larger rating and losses
- Only the load-carrying bridge fires
- Dead time of a few ms at reversal
- Needs a current sensor and logic
A DC drive needs torque and speed of either sign — four quadrants. One thyristor bridge can give V_dc of either sign but I_d of one sign only (thyristors conduct one way), so two bridges…
Key takeaways
- Three-phase bridge: V_dc = (3√2/π)V_LL = 1.35V_LL, ripple 6f, 120° conduction, PIV = √2V_LL; thyristor version V_dc ∝ cos α, negative (inversion) for α > 90°.
- Source reactance causes overlap: ΔV = 3X_sI_d/π and cos α − cos(α + μ) = 2X_sI_d/(√2V_LL); the drop dissipates no power.
- Six-pulse line current has harmonics only at 6k ± 1 with I_n = I₁/n and I₁ = (√6/π)I_d; the n-th harmonic lags by nα; THD = 31.1% (three-phase), 48.3% (single-phase bridge).
- PF = distortion factor × displacement factor; DF = 3/π = 0.955 (three-phase) or 2√2/π = 0.9 (single-phase), independent of α; displacement factor = cos α.
- Dual converters (anti-parallel bridges, α₁ + α₂ = 180° with circulating current) give four-quadrant DC drives; the PWM voltage-source converter is a boost converter (V_dc ≥ √2V_LL) with sinusoidal, unity-power-factor, bidirectional line current.
Practice questions (24)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
The mean output voltage of an uncontrolled three-phase bridge rectifier supplied at line voltage V_LL (rms) is:
Show answer
Answer: A — (3√2/π) V_LL ≈ 1.35 V_LL
The output is the envelope of the line-to-line voltages: V_dc = (6/2π)∫ √2 V_LL cos θ dθ over ±30° = (3√2/π)V_LL. 0.9 V is the single-phase bridge, and √2 V_LL is the peak, not the mean.The ripple frequency at the output of a three-phase full-wave bridge fed from a 50 Hz supply is:
Show answer
Answer: B — 300 Hz
Six humps per supply cycle give a ripple at 6 × 50 = 300 Hz. A single-phase bridge ripples at 2f = 100 Hz and a three-phase half-wave rectifier at 3f = 150 Hz.A three-phase fully controlled bridge on a 400 V (line) supply is fired at α = 60°. Ignoring source inductance, find the mean output voltage in volts (nearest integer).
Numerical answer — type the value.
Show answer
Answer: 270
V_dc = 1.3505 × 400 × cos 60° = 540.2 × 0.5 = 270.1 V.
Show the other 21 questions
A controlled three-phase bridge operates with firing angle α = 120° into a load that includes a regenerating DC machine. The converter is operating as:
Show answer
Answer: C — an inverter, with negative mean DC voltage and power returned to the AC line
V_dc ∝ cos α is negative for α > 90°; with a source of the right polarity on the DC side the mean power is negative, i.e. flows from DC to AC — line-commutated inverter operation.A 400 V (line) three-phase fully controlled bridge with α = 30°, source reactance 0.2 Ω per phase and I_d = 50 A has a mean output voltage nearest to:
Show answer
Answer: D — 458.3 V
ΔV = 3 X_s I_d/π = 3 × 0.2 × 50/π = 9.55 V; V_dc = 467.8 − 9.55 = 458.3 V. The 437.8 V option omits the 1/π factor.For a three-phase six-pulse converter with a large DC-side inductance, the characteristic line-current harmonics are:
Show answer
Answer: A — n = 6k ± 1 (5, 7, 11, 13, …) with magnitude I₁/n
The 120° quasi-square phase current has no triplen or even harmonics in a balanced three-wire system; the harmonic amplitudes fall as 1/n. The numerical Fourier analysis in this chapter confirmed I₅ = I₁/5, I₇ = I₁/7 and zero at 2, 3 and 4.The distortion factor of the line current of a three-phase bridge converter with a large DC inductance (independent of firing angle) is:
Show answer
Answer: D — 3/π = 0.955
DF = I₁/I_rms = (√6/π I_d)/(√(2/3) I_d) = 3/π = 0.9550. 2√2/π is the single-phase bridge, cos α is the displacement factor, and PF = DF × cos α.Find the input power factor of a three-phase bridge converter with large DC inductance at a firing angle of 30° (distortion factor 3/π). Give the answer to two decimals.
Numerical answer — type the value.
Show answer
Answer: 0.83
PF = (3/π) cos 30° = 0.9550 × 0.8660 = 0.827. Using cos α alone would give 0.87, forgetting that the waveform itself is distorted.In a dual converter operated with circulating current, the firing angles of the two bridges satisfy:
Show answer
Answer: A — α₁ + α₂ = 180°
With α₁ + α₂ = 180° the mean voltages V₀cos α₁ and V₀cos α₂ are equal and opposite, so no DC circulating current flows, only ripple current limited by the inter-group reactor.A three-phase PWM boost rectifier (active front end) operates from a 400 V line-to-line supply. The minimum DC-link voltage required for controlled sinusoidal-current operation is nearest to:
Show answer
Answer: D — 566 V
The bridge can only synthesise voltages up to V_dc/2 per phase, so V_dc must exceed the peak line voltage √2 × 400 = 565.7 V; a practical design adds 10–20% margin. A diode bridge alone would give 540 V.A three-phase half-wave (three-pulse) diode rectifier is fed from a 50 Hz supply. The fundamental ripple frequency of its output, in Hz, is ____.
Numerical answer — type the value.
Show answer
Answer: 150
The ripple frequency is the pulse number times the supply frequency: 3 × 50 = 150 Hz. The tempting 300 Hz belongs to the six-pulse bridge.In a three-phase diode bridge with a ripple-free DC load current, each diode conducts for how many degrees of every supply cycle? ____
Numerical answer — type the value.
Show answer
Answer: 120
Each of the six diodes is the most positive (or most negative) of its group for one third of the cycle, i.e. 120 degrees, and a pair conducts for every 60-degree interval. The tempting 60 degrees is the length of one commutation interval, not one diode’s conduction.A freewheeling diode is connected across the inductive load of a phase-controlled rectifier. Its main effect is to
Show answer
Answer: C — prevent the output voltage from going negative
When the supply voltage reverses, the load current transfers to the diode, clamping the output near zero, which raises the average voltage and improves the power factor. Inverting operation is the tempting opposite: it needs negative output voltage, which the diode forbids.The lowest characteristic AC-side current harmonic of a 12-pulse converter is the
Show answer
Answer: D — 11th
Characteristic harmonics are h = kp ± 1; with p = 12 the first are 11 and 13, because the phase-shifted transformers cancel the 5th and 7th of the two six-pulse bridges. The tempting 5th is the lowest harmonic of a single six-pulse bridge.A separately excited DC motor must be driven and braked regeneratively in both directions of rotation from an AC supply. The converter arrangement needed is
Show answer
Answer: A — a dual converter (two fully controlled bridges in antiparallel)
Four-quadrant operation needs both polarities of current as well as of voltage; one bridge conducts current in one direction only, so two are placed in antiparallel. A single full bridge tempts because it reaches two quadrants (both voltage signs), but not reverse current.A three-phase half-controlled bridge on a 400 V (line) supply is fired at α = 60 degrees with continuous load current. Its average output voltage, in V to the nearest integer, is ____.
Numerical answer — type the value.
Show answer
Answer: 405
V_dc = (1.35V_LL/2)(1 + cos α) = 270.1 × 1.5 = 405 V. The tempting 270 V applies the fully controlled formula 1.35V_LL cos α.A three-phase bridge converter carries a ripple-free DC current of 100 A. The RMS value of its AC line current, in A to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 81.6
Each line carries ±I_d for 120 degrees of every 180, so I_rms = I_d√(2/3) = 81.6 A. The tempting 100 A assumes current flows all the time.For the same bridge with I_d = 100 A, the RMS value of the 5th harmonic of the line current, in A to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 15.6
The fundamental is (√6/π)I_d = 78.0 A and the characteristic harmonics fall as 1/h, so I₅ = 78.0/5 = 15.6 A, which an FFT of the stepped waveform confirms. The tempting 20 A divides I_d itself by 5.A bidirectional DC-DC converter links a 240 V battery to a 400 V DC bus. When it returns power from the battery to the bus, it acts as a boost stage. The duty cycle of its active (lower) switch, ideally, is ____.
Numerical answer — type the value.
Show answer
Answer: 0.4
Boost: V_bus = V_bat/(1 − D), so D = 1 − 240/400 = 0.4. The tempting 0.6 is 240/400, the duty of the upper switch when the same leg bucks power into the battery.A three-phase fully controlled bridge on a 415 V (line) supply must deliver an average of 280 V to a load with continuous current, ignoring overlap. The firing angle needed, in degrees to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 60
V_d0 = (3√2/π) × 415 = 560.4 V, so cos α = 280/560.4 = 0.4996 and α = 60.0 degrees. The tempting 47.6 degrees uses the half-wave constant 1.17 with the line voltage.A three-phase fully controlled bridge on 400 V (line) carries a ripple-free 100 A at a firing angle of 60 degrees. The fundamental reactive power drawn from the supply, in kVAR to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 46.8
Q₁ = V_d0 I_d sin α = 540.2 × 100 × 0.866 = 46.8 kVAR (and P = V_d0 I_d cos α = 27.0 kW). The tempting 27.0 kVAR uses cos α, which gives the real power.An uncontrolled three-phase bridge is fed at 400 V (line) and carries a ripple-free load current with no output filter capacitor. The peak-to-peak ripple of its output voltage, in V to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 75.8
The output follows the line-voltage peaks between 60 and 120 degrees, swinging from √2V_LL to √2V_LL cos 30°: 565.7 × (1 − 0.866) = 75.8 V. The tempting 565.7 V treats the output as if it fell to zero, as in a single-phase rectifier.For a six-pulse bridge with a ripple-free DC current, the total harmonic distortion of the AC line current, in per cent to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 31.1
I_rms/I₁ = √(2/3)/(√6/π) = π/3, so THD = √(π²/9 − 1) = 31.1 per cent. The tempting 4.5 per cent is 1 − 3/π, a misuse of the distortion factor 3/π as if it were the THD.A DC machine with a back EMF of 400 V regenerates through a three-phase fully controlled bridge on a 415 V (line) supply. Its armature resistance is 0.5 ohm and the returned current is 40 A, with overlap ignored. The firing angle needed, in degrees to one decimal place, is ____.
Numerical answer — type the value.
Show answer
Answer: 132.7
In inversion the converter must hold V_dc = −(E − I_aR_a) = −380 V, so cos α = −380/560.4 and α = 132.7 degrees. The tempting 135.5 degrees uses −400 V, forgetting that the armature drop reduces the voltage reaching the bridge.