Machines in Operation: Parallel Transformers, DC Speed Control, Induction Starting and Synchronous Operation

The Electrical Machines line asks for much more than the equivalent circuits: transformer vector groups and parallel operation, motoring and generating DC machines and the speed control of DC motors, the starting and speed control of induction machines, and the regulation, parallel operation and starting of synchronous machines. The first Machines chapter taught the equivalent circuits, the open- and short-circuit tests and the torque–slip curve; this one is about using the machine. Every topic has the same two-part structure: a condition (what must match before you connect, or what you may not do) and a sharing or control rule (how load divides, how speed responds). Parallel transformers must match voltage ratio, polarity and phase displacement, and then share load in proportion to rating over per-unit impedance. A DC motor's speed is (V − I_a R_a)/Kφ, so all its speed control is a choice of which of the three to move. An induction motor's starting current falls with the voltage squared as the torque does, and its starting torque can be raised only by raising rotor resistance. A synchronous machine's power is EV sinδ/X for a round rotor and carries an extra reluctance term for a salient pole. Computed values: two parallel transformers of 500 kVA/4% and 250 kVA/5% carry a 700 kVA total before the first one is full; a shunt motor with 2 Ω added in the armature drops from 1000 to 810 rpm; and a salient-pole machine's maximum power occurs at 67.2°, not 90°.
Overview

Transformers in Parallel: Four Conditions and the Sharing Rule

2 min read · 2 parts

Connecting two transformers in parallel requires (1) the same voltage ratio (otherwise a circulating current flows at no load), (2) the same polarity (otherwise a dead short across the secondaries), (3) the same phase sequence and phase displacement between primary and secondary — fixed by the vector group, so a Dyn11 can be paralleled with another Dyn11 and not with a Dyn1 or a Yy0 — and (4) for good sharing, equal per-unit (percentage) impedances on their own ratings with similar X/R. Groups with the same displacement class can be paralleled: Yy0 with Dd0 (both 0°) and Dy1 with Yd1 (both −30°), while Yd1 and Yd11 differ by 60° and cannot. Given matched ratios and displacement, the load shares as S_rated / z_pu: S_A : S_B = (S_A,rated/z_A) : (S_B,rated/z_B). So the transformer with the lower per-unit impedance carries more than its fair share and reaches full load first.

Worked example. A 500 kVA unit with z = 4% and a 250 kVA unit with z = 5% supply 600 kVA. The shares are proportional to 500/4 = 125 and 250/5 = 50, so A takes 600 × 125/175 = 428.6 kVA and B 171.4 kVA — A is at 85.7% of its rating and B at 68.6%. The total that can be supplied without overloading either is found when A reaches 500 kVA: then B carries 500 × 50/125 = 200 kVA, so the pair is limited to 700 kVA against a nameplate sum of 750 kVA — a 6.7% shortfall caused by the unequal impedances. The vector sum of the sharing in practice is slightly below the arithmetic sum when the X/R ratios differ, because the two currents are then out of phase.

GroupPhase displacement (LV w.r.t. HV)Can parallel with
Yy0, Dd0, Dz00°any other 0° group
Dy1, Yd1−30° (lag)other −30° groups only
Dy11, Yd11, Dyn11+30° (lead)other +30° groups only
Yd1 against Yd1160° apartcannot — a 60° voltage difference gives a heavy circulating current
Four conditions for paralleling transformers
Transformers in parallel
  • Same voltage ratioElse circulating current at no load
  • Same polarityElse a dead short across secondaries
  • Same phase sequence and displacementFixed by the vector group
  • Equal per-unit impedance, similar X/RFor good load sharing

Connecting two transformers in parallel requires (1) the same voltage ratio (otherwise a circulating current flows at no load), (2) the same polarity (otherwise a dead short across the…

DC Motors: Speed Control, Characteristics and Braking

2 min read · 2 parts

For any DC machine E_b = K φ ω, and for a motor V = E_b + I_a R_a, so speed N ∝ (V − I_a R_a)/φ. Torque is T = K φ I_a. The three speed-control methods move one term each. Armature-voltage control (variable V, Ward–Leonard or a chopper/converter) changes speed smoothly below base speed at constant flux, hence constant torque. Field control (weaken φ) raises speed above base speed, hence constant power since E_b I_a stays about the same. Armature-resistance control wastes I_a² R_series and gives poor speed regulation. Example: a 220 V shunt motor with R_a = 0.5 Ω draws 20 A at 1000 rpm, so E_b = 210 V. Adding 2 Ω in series at the same torque (same I_a, constant flux): E_b = 220 − 20 × 2.5 = 170 V and N = 1000 × 170/210 = 810 rpm. A starter is needed because at standstill E_b = 0 and I_a = V/R_a = 440 A — 22 times the rated current.

MotorCharacteristicCaution
Shuntnearly constant speed; T ∝ I_anever open the field circuit — speed runs away
SeriesT ∝ I_a² (unsaturated); high starting torque; speed falls with loadnever start at no load — dangerous overspeed
Compound (cumulative)between shunt and seriesdifferential compounding can be unstable

Generating mode and braking. A DC machine generates when E_b > V: the armature current reverses and the machine returns power. Regenerative braking (a downhill train, a lowered crane load) keeps the machine on the line while the load drives it faster than no-load speed; dynamic (rheostatic) braking disconnects the supply and dissipates the energy in a resistor across the armature; plugging reverses the supply terminals and gives strong braking at heavy current loss. The armature of a series motor must have its connection reversed relative to the field when it is braked regeneratively, since the field current would otherwise reverse with the armature current and kill the flux.

Three ways to brake a DC motor
Braking
  • RegenerativeStays on the line; returns power
  • Dynamic (rheostatic)Supply off; energy in a resistor
  • PluggingSupply reversed; strong, heavy current loss

For any DC machine E_b = K φ ω, and for a motor V = E_b + I_a R_a, so speed N ∝ (V − I_a R_a)/φ. Torque is T = K φ I_a. The three speed-control methods move one term each. Armature-voltage…

Induction Motors: Starting and Speed Control

2 min read · 2 parts

At standstill (s = 1) an induction motor is a short-circuited transformer, so the starting current is 5–7 times rated while the starting torque is only about 1–2 times. Direct-on-line (DOL) starting is acceptable only for small motors or strong supplies. Star–delta starting applies V/√3 to each phase, so the line current falls to 1/3 and the torque, ∝ V², to 1/3 of DOL — the torque is therefore reduced exactly as much as the current, and it works only for motors normally delta-connected and unloaded at start. An autotransformer with ratio k reduces the motor voltage to kV: motor current ∝ k, supply current ∝ k² (the transformer steps it back down) and torque ∝ k²; at k = 0.8 both fall to 64%. A wound-rotor motor adds external rotor resistance, which does not change the maximum torque but moves it to a higher slip, since s_m = R₂/X₂, so with the right resistance the maximum torque occurs at starting (s_m = 1) and the starting torque is raised — the only starting method that improves torque while reducing current.

Torque–slip shape. Neglecting stator impedance, T/T_max = 2 / (s/s_m + s_m/s). With s_m = 0.25 and a full-load slip of 0.04: T_fl = 0.312 T_max and T_start = 0.471 T_max, so this motor starts with 1.51 times full-load torque on DOL and 0.50 times on star–delta — less than full-load torque, which is why a star–delta start must be unloaded. Speed control follows ω_m = ω_s(1 − s) with ω_s = 4π f/P: here 1500 rpm for 4 poles at 50 Hz. Methods: V/f control (keep the flux constant, torque capability constant below base speed; the standard drive method), rotor-resistance control (wound rotor only; wastes power as s P_gap), pole changing (stepped, squirrel cage), stator-voltage control (poor, narrow range) and, for wound rotors, slip-power recovery.

Reduced-voltage starting compared with DOL
Star–delta
  • V/√3 per phase
  • Line current 1/3 of DOL
  • Torque 1/3 of DOL
Autotransformer, ratio k
  • Motor voltage kV
  • Supply current ∝ k²
  • Torque ∝ k²; at k = 0.8, 64%

At standstill (s = 1) an induction motor is a short-circuited transformer, so the starting current is 5–7 times rated while the starting torque is only about 1–2 times. Direct-on-line (DOL)…

Synchronous Machines: Salient Poles, Parallel Operation, V-Curves and Starting

2 min read · 2 parts

A cylindrical-rotor machine delivers P = (E V / X_s) sin δ, maximum at δ = 90°. A salient-pole machine has different reactances along the pole (direct axis, X_d) and between poles (quadrature axis, X_q < X_d), and (two-reaction theory) delivers P = (E V / X_d) sin δ + (V²/2)(1/X_q − 1/X_d) sin 2δ. The second, reluctance term exists even at zero excitation and makes the maximum power occur at δ < 90°. Per unit with X_d = 1, X_q = 0.6, V = 1 and E = 1.2: P_max = 1.3444 at δ = 67.2°, against 1.200 at 90° for a round rotor of the same X_d — the salient machine gains 12.0% in peak power. With no excitation (E = 0) it still develops a reluctance power of up to 0.333 pu, which is the principle of the reluctance motor.

Parallel operation of alternators (synchronising) needs four matches before closing the breaker: equal terminal voltage, equal frequency, the same phase sequence and zero phase difference (checked by synchroscope or lamps). After closing, the prime-mover governor setting shares real power and the field current shares reactive power: raising one machine's governor input moves load onto it, while raising its excitation makes it supply more lagging reactive power. Two machines' droops decide the sharing: a 4% droop machine takes load in proportion to its rating if all machines have equal droop. V-curves plot armature current against field current at constant power: the minimum current is at unity power factor; to the left (under-excited) the current lags, to the right (over-excited) it leads — so an over-excited synchronous motor draws leading current and can correct the power factor of the plant (a synchronous condenser when run unloaded). The inverted V-curve shows power factor against excitation. Starting: a synchronous motor produces no average torque at standstill, so it is started as an induction motor using damper (amortisseur) windings, with the field winding shorted through a resistor (to avoid dangerous induced voltage and the single-phase-like pulsating torque), then excited when speed reaches about 95% of synchronous for pull-in. Alternatives are a pony motor or a variable-frequency drive.

🎯 Sharing between transformers, worked
Transformers in parallel share a load in proportion to rating divided by per-unit impedance. A 100 kVA unit with Z = 4% and a 200 kVA unit with Z = 5% carrying 240 kVA together have weights 100/4 = 25 and 200/5 = 40, total 65, so the first carries 240 × 25/65 = 92.3 kVA and the second 147.7 kVA. The 100 kVA unit takes 92.3% of its rating and the 200 kVA unit 73.8%, so the lower-impedance unit reaches full load first and sets the total that can be carried without overload.

A cylindrical-rotor machine delivers P = (E V / X_s) sin δ, maximum at δ = 90°. A salient-pole machine has different reactances along the pole (direct axis, X_d) and between poles…

Key takeaways

  • Parallel transformers need equal voltage ratio, polarity, phase sequence and vector-group displacement; load shares as S_rated/z_pu, so the lower-impedance unit overloads first and the pair cannot give its nameplate sum.
  • DC motor speed N ∝ (V − I_aR_a)/φ: armature-voltage control below base speed (constant torque), field control above (constant power), series resistance wastes power; starting current is V/R_a.
  • Star–delta cuts both starting current and torque to one third; an autotransformer at ratio k gives k² of both; only rotor resistance raises starting torque, because s_m = R₂/X₂ moves up.
  • Salient-pole power adds a reluctance term (V²/2)(1/X_q − 1/X_d) sin 2δ, so maximum power occurs below 90°; alternators synchronise on voltage, frequency, sequence and phase; governor shares kW, excitation shares kVAr.
  • An over-excited synchronous motor draws leading current (V-curve right side) and corrects power factor; it has no starting torque and starts with damper windings.

Practice questions (24)

Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.

  1. Which of the following is NOT a condition for paralleling two single-phase transformers?

    1. equal per-unit impedances for good load sharing
    2. equal kVA ratings
    3. equal voltage ratios
    4. correct polarity
    Show answer

    Answer: B — equal kVA ratings

    Ratings need not match: transformers of different kVA share load in proportion to rating provided the per-unit impedances (on their own ratings) are equal. Voltage ratio and polarity are essential to avoid circulating current and a short.
  2. Transformers of 500 kVA (z = 4%) and 250 kVA (z = 5%) operate in parallel with equal voltage ratios. For a total load of 600 kVA, the 500 kVA unit supplies about:

    1. 400 kVA
    2. 300 kVA
    3. 500 kVA
    4. 429 kVA
    Show answer

    Answer: D — 429 kVA

    Shares go as S/z: 500/4 = 125 and 250/5 = 50, so the larger unit takes 600 × 125/175 = 428.6 kVA. The 400 kVA option is the split by rating alone (2:1), which would be right only for equal per-unit impedances.
  3. A 220 V shunt motor with R_a = 0.5 Ω runs at 1000 rpm taking 20 A. If 2 Ω is added in series with the armature and the torque (so I_a, with constant flux) is unchanged, the new speed is nearest to:

    1. 773 rpm
    2. 1000 rpm
    3. 810 rpm
    4. 952 rpm
    Show answer

    Answer: C — 810 rpm

    E_b before = 220 − 20 × 0.5 = 210 V; after = 220 − 20 × 2.5 = 170 V. With flux constant, speed ∝ E_b, so N = 1000 × 170/210 = 809.5 rpm.
Show the other 21 questions
  1. Speed of a DC motor above its base speed is obtained by:

    1. adding armature series resistance
    2. increasing the field flux
    3. weakening the field (constant-power region)
    4. reducing the armature voltage
    Show answer

    Answer: C — weakening the field (constant-power region)

    N ∝ (V − I_aR_a)/φ; with V already at its rated value, only reducing φ can raise N. Torque (∝ φ I_a) then falls, so the region is constant power.
  2. A three-phase induction motor is started with a star–delta starter. Compared with direct-on-line starting, the starting line current and starting torque become:

    1. one half and one quarter
    2. one third and one third
    3. one third and one ninth
    4. one ninth and one third
    Show answer

    Answer: B — one third and one third

    Phase voltage is V/√3, so phase current and torque (∝ V²) fall to 1/3 of the delta values; the line current in star equals the phase current, which is one third of the delta line current (√3 × phase current). So both are 1/3.
  3. Inserting external resistance in the rotor circuit of a wound-rotor induction motor:

    1. reduces the maximum torque and leaves its slip unchanged
    2. shifts the maximum torque to a lower slip
    3. raises the maximum torque in proportion
    4. leaves the maximum torque unchanged and shifts it to a higher slip
    Show answer

    Answer: D — leaves the maximum torque unchanged and shifts it to a higher slip

    T_max = 3V²/(2ω_s(R₁ + √(R₁² + X²))) does not contain R₂, while s_m = R₂/X₂ is proportional to it. Hence the rotor-resistance starter moves the peak towards s = 1 and raises starting torque without changing the peak.
  4. A salient-pole synchronous generator has X_d = 1.0 pu, X_q = 0.6 pu, terminal voltage 1.0 pu and E = 1.2 pu. Using P = (EV/X_d) sin δ + (V²/2)(1/X_q − 1/X_d) sin 2δ, find the maximum power in pu to two decimals.

    Numerical answer — type the value.

    Show answer

    Answer: 1.34

    P(δ) = 1.2 sin δ + 0.3333 sin 2δ. Setting dP/dδ = 0 numerically gives δ = 67.2° and P_max = 1.3444 pu, above the 1.2 pu a round rotor of the same X_d would give at 90°.
  5. An over-excited synchronous motor on a plant bus draws current that is:

    1. zero
    2. leading, so it improves the plant power factor
    3. lagging, so it worsens the power factor
    4. exactly in phase with the voltage
    Show answer

    Answer: B — leading, so it improves the plant power factor

    Over-excitation makes E > V cos δ, so the machine supplies reactive power to the bus, like a capacitor. At the minimum of the V-curve the current is at unity power factor; to its right it leads.
  6. Why is a synchronous motor not self-starting?

    1. It has no stator winding
    2. At standstill the rotating stator field passes the rotor too fast for the rotor poles to lock, so the average torque is zero
    3. Its armature resistance is too high
    4. Its rotor flux is zero at standstill
    Show answer

    Answer: B — At standstill the rotating stator field passes the rotor too fast for the rotor poles to lock, so the average torque is zero

    The stator field rotates at synchronous speed while the rotor is stationary; the torque on a rotor pole alternates in sign twice per slip cycle, averaging to zero. Damper windings supply induction-motor torque to bring it near synchronous speed first.
  7. Armature-voltage control of a separately excited DC motor at rated field is used to obtain

    1. speeds above base speed at constant power
    2. speeds below base speed at constant torque capability
    3. only a single fixed speed
    4. reversal of the field flux
    Show answer

    Answer: B — speeds below base speed at constant torque capability

    With full flux, rated current gives rated torque at every armature voltage, and N ∝ V_a below base speed. Constant-power operation above base speed is the tempting description of field weakening.
  8. A DC motor runs at 1000 rpm. Its field flux is reduced to 80 per cent while the back EMF is held constant. The new speed, in rpm, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 1250

    N ∝ E_b/φ, so N = 1000/0.8 = 1250 rpm. The tempting 800 rpm assumes speed falls with flux, which is the generator intuition reversed.
  9. A rotor-resistance starter can be used only with

    1. synchronous motors
    2. DC series motors
    3. squirrel-cage induction motors
    4. slip-ring (wound-rotor) induction motors
    Show answer

    Answer: D — slip-ring (wound-rotor) induction motors

    External resistance has to be connected to the rotor winding through slip rings and brushes. A squirrel cage, the tempting choice because it is the commonest motor, has short-circuited bars with no access.
  10. An autotransformer starter applies 60 per cent of line voltage to an induction motor. The starting line current, as a fraction of the direct-on-line starting current, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 0.36

    Motor current falls to x = 0.6 of DOL and the autotransformer steps line current down by another factor x, giving x² = 0.36. The tempting 0.6 is the motor-side current, not the line current.
  11. Two alternators share a load in parallel on an infinite bus. To make one of them take a larger share of the real power, the operator

    1. changes its phase sequence
    2. increases its field excitation
    3. increases the mechanical input from its prime mover
    4. reduces its field excitation
    Show answer

    Answer: C — increases the mechanical input from its prime mover

    Real power comes from the prime mover; opening the governor advances the load angle and the machine picks up load. Changing excitation, the tempting option, only shifts reactive power and the power factor.
  12. In the V-curves of a synchronous motor at constant load, the armature current is minimum when the motor operates at

    1. maximum lagging power factor
    2. zero excitation
    3. unity power factor
    4. maximum leading power factor
    Show answer

    Answer: C — unity power factor

    At constant power, I = P/(3V cos φ) is least when cos φ = 1, the bottom of the V. Under- or over-excitation adds a reactive component, which is why both leading and lagging operation tempt but give larger currents.
  13. A 220 V shunt motor (R_a = 0.4 ohm) runs at 1000 rpm with an armature current of 50 A. The field is weakened to 90 per cent of its flux while the load torque stays constant. The new speed, in rpm to the nearest integer, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 1099

    Constant torque needs I_a = 50/0.9 = 55.6 A; E_b falls from 200 V to 220 − 22.2 = 197.8 V; N = 1000 × (197.8/200)/0.9 = 1099 rpm. The tempting 1111 rpm assumes the back EMF stays at 200 V, ignoring the extra armature drop.
  14. An induction motor develops a direct-on-line starting torque of 1.8 times full-load torque. If it is started through an autotransformer at 70 per cent tapping, its starting torque, as a multiple of full-load torque, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 0.882

    Torque varies as V², so T_st = 0.7² × 1.8 = 0.882 of full-load torque. The tempting 1.26 scales torque linearly with voltage.
  15. Two generators with linear governor droop share a 1000 kW load. Generator 1 runs at 51 Hz on no load and drops 1 Hz per 250 kW; generator 2 runs at 51.5 Hz on no load and drops 1 Hz per 200 kW. The common operating frequency, in Hz, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 49

    51 − P₁/250 = 51.5 − (1000 − P₁)/200 gives P₁ = 500 kW, so f = 51 − 2 = 49 Hz (generator 2 also carries 500 kW). The tempting 50 Hz assumes the nominal frequency is held, which droop control does not do.
  16. A cylindrical-rotor synchronous motor has E = 1.2 pu, V = 1.0 pu and X_s = 0.8 pu, with negligible resistance. The power it converts at a load angle of 30 degrees, in pu, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 0.75

    P = (EV/X_s) sin δ = 1.5 × 0.5 = 0.75 pu. The tempting 1.3 pu uses cos δ, and 1.5 pu is the pull-out maximum at δ = 90 degrees.
  17. A plant draws 1000 kW at 0.8 power factor lagging. A synchronous condenser is to raise the power factor to 0.95 lagging with the real power unchanged. The leading kVAR it must supply, to the nearest integer, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 421

    Q₁ = 1000 tan(cos⁻¹ 0.8) = 750 kVAR and Q₂ = 1000 tan(cos⁻¹ 0.95) = 329 kVAR, so the condenser supplies 421 kVAR. The tempting 750 kVAR corrects all the way to unity power factor.
  18. Which of the following methods reduce the starting line current of a three-phase induction motor?

    1. Star–delta starting
    2. Autotransformer starting
    3. Direct-on-line starting
    4. Rotor-resistance starting of a slip-ring motor
    Show answer

    Answer: A — Star–delta starting; B — Autotransformer starting; D — Rotor-resistance starting of a slip-ring motor

    Star–delta and autotransformer starting lower the applied voltage, and added rotor resistance raises the rotor impedance at standstill. DOL, the tempting fourth, applies full voltage and draws the largest starting current, typically 5 to 7 times full load.
  19. An unsaturated 220 V DC series motor (total resistance 0.5 ohm) runs at 1000 rpm drawing 20 A. The load torque is halved. Taking flux proportional to current, the new speed, in rpm to the nearest integer, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 1434

    T ∝ I², so I = 20/√2 = 14.14 A; E = 220 − 7.07 = 212.9 V; N = 1000 × (212.9/210) × (20/14.14) = 1434 rpm. The tempting 2000 rpm assumes current halves with torque, as in a shunt motor.
  20. Two single-phase transformers are paralleled with slightly unequal ratios, so that on no load their secondary EMFs are 410 V and 400 V. Their leakage impedances referred to the secondary are 0.10 ohm and 0.15 ohm (taken as purely resistive here). The no-load circulating current, in A, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 40

    The 10 V difference drives current around the loop through both impedances in series: I_c = 10/(0.10 + 0.15) = 40 A, even with no load connected. The tempting 100 A uses only the smaller impedance.
  21. A cylindrical-rotor synchronous motor (X_s = 1.0 pu, negligible resistance) on a 1.0 pu bus takes 0.5 pu real power at unity power factor. Its excitation EMF, in pu to two decimal places, is ____.

    Numerical answer — type the value.

    Show answer

    Answer: 1.12

    For a motor E = V − jX_sI = 1 − j0.5, so |E| = 1.12 pu, lagging V by 26.6 degrees. The tempting 1.5 pu adds X_sI arithmetically, ignoring the quadrature.