Heat Transfer at Working Depth: Composite and Cylindrical Conduction, Lumped and Semi-Infinite Transients, Fins, Convection Correlations, Radiation Networks, Condensation, Exchanger Design and Evaporators
Convection Coefficients and Radiation
Dimensionless groups: Nu = hL/k, Re = ρVL/μ, Pr = c_pμ/k, Gr = gβΔTL³/ν², and Ra = Gr·Pr for natural convection. Fully developed laminar tube flow gives Nu = 3.66 (constant wall temperature) or 4.36 (constant flux), independent of Re. Turbulent tube flow uses Dittus–Boelter Nu = 0.023Re^0.8Pr^n (n = 0.4 heating, 0.3 cooling) for Re > 10⁴. Example: water at 40 °C (ρ = 992, μ = 6.53×10⁻⁴ Pa·s, k = 0.63, c_p = 4179) at 1 m/s in a 25 mm tube: Re = 37,979, Pr = 4.33, Nu = 190.6, h = 4802 W/m²K. For laminar flow over a flat plate Nu_L = 0.664Re_L^(1/2)Pr^(1/3) averaged over L, twice the local value at the end. Because h ∝ V^0.8, doubling the velocity raises h by 2^0.8 = 1.74 and the pressure drop about fourfold.
Radiation. Black-body emissive power E_b = σT⁴ with σ = 5.67×10⁻⁸ W/m²K⁴; a grey surface has ε = α (Kirchhoff). For two large parallel grey plates the net exchange is q = σ(T₁⁴ − T₂⁴)/(1/ε₁ + 1/ε₂ − 1). With ε₁ = 0.8, ε₂ = 0.5, T₁ = 500 K, T₂ = 300 K the effective emissivity is 0.444 and q = 1371 W/m². One thin shield (ε = 0.5 on both faces) between them adds two surface resistances: q = σ(T₁⁴ − T₂⁴)/[(1/ε₁ + 1/ε_s − 1) + (1/ε_s + 1/ε₂ − 1)] = 588 W/m², a reduction to 43%. View factors obey reciprocity A₁F₁₂ = A₂F₂₁ and summation ΣF_ij = 1; a convex body has F₁₁ = 0. A radiation heat-transfer coefficient is h_r = εσ(T₁² + T₂²)(T₁ + T₂). Gases such as CO₂ and H₂O absorb and emit in bands, so a hot flue gas radiates, while air does not.
| Quantity | Value |
|---|---|
| Water, 25 mm tube, 1 m/s: Re / Pr / Nu | 37,979 / 4.33 / 190.6 |
| Dittus–Boelter h | 4802 W/m²K |
| Parallel plates ε = 0.8, 0.5; 500 K, 300 K | 1371 W/m² |
| With one ε = 0.5 shield | 588 W/m² |
Dimensionless groups: Nu = hL/k, Re = ρVL/μ, Pr = c_pμ/k, Gr = gβΔTL³/ν², and Ra = Gr·Pr for natural convection. Fully developed laminar tube flow gives Nu = 3.66 (constant wall…
Condensation, Boiling and Evaporators
Film condensation on a vertical plate (Nusselt): h̄ = 0.943[ρ_l(ρ_l − ρ_v)g h_fg k³/(μ L ΔT)]^(1/4). For saturated steam at 100 °C (ρ_l = 958, h_fg = 2257 kJ/kg, k_l = 0.68, μ_l = 2.82×10⁻⁴) on a 1 m plate with ΔT = 10 K: h̄ = 6,506 W/m²K; h falls as ΔT^(−1/4) and as L^(−1/4); on horizontal tubes the factor is 0.725 with D replacing L, so horizontal tubes beat vertical ones. Dropwise condensation gives coefficients several times higher but is hard to sustain. Non-condensable gas in steam sharply lowers h. Boiling passes through natural convection, nucleate boiling (high h, rising as ΔT_e^3), a critical heat flux (about 1.1 MW/m² for water at 1 atm, the burnout point), a transition regime and stable film boiling; equipment is operated in the nucleate regime below the critical flux.
Evaporators. Concentrating 10 000 kg/h of feed from 5% to 20% solids evaporates E = F(1 − x_F/x_P) = 7500 kg/h. A single effect with steam at latent heat 2257 kJ/kg (feed at its boiling point, no boiling-point rise) needs about 7500 kg/h of steam (economy ≈ 1) and duty Q = 4.70 MW; with U = 2000 W/m²K and ΔT = 40 K the area is A = Q/(UΔT) = 58.8 m². A triple effect with the same total ΔT splits it into 13.3 K per effect; each effect evaporates ~2500 kg/h (economy ≈ 3, steam ≈ 2500 kg/h), each has Q = 1.567 MW and A = 58.8 m², so the total area is 176.3 m², 3 times the single effect. More effects save steam but cost area; the optimum balances steam against capital, and boiling-point rise and hydrostatic head eat into the usable ΔT. Forward feed suits hot feed, backward feed suits viscous liquors.
| Quantity | Value |
|---|---|
| Film condensation, steam on 1 m plate, ΔT = 10 K | 6,506 W/m²K |
| Water evaporated, 5% → 20%, 10 000 kg/h | 7500 kg/h |
| Single-effect area (U = 2000, ΔT = 40 K) | 58.8 m² |
| Triple-effect total area, same ΔT | 176.3 m² |
Film condensation on a vertical plate (Nusselt): h̄ = 0.943[ρ_l(ρ_l − ρ_v)g h_fg k³/(μ L ΔT)]^(1/4). For saturated steam at 100 °C (ρ_l = 958, h_fg = 2257 kJ/kg, k_l = 0.68, μ_l =…
Heat Exchanger Design: LMTD, Correction Factor, Fouling and NTU
The design equation is Q = UAΔT_lm with ΔT_lm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂). Example: hot oil (2 kg/s, c_p = 2100 J/kg·K) cooled from 150 °C to 90 °C against water heated from 30 °C to 70 °C: Q = 2 × 2100 × 60 = 252 kW. Counter-current: ΔT₁ = 150 − 70 = 80, ΔT₂ = 90 − 30 = 60, ΔT_lm = 69.52 K; co-current: ΔT₁ = 120, ΔT₂ = 20, ΔT_lm = 55.81 K, much smaller, so counter-current needs less area and can cross temperatures. For U = 500 W/m²K, a double-pipe unit in counter-flow needs A = Q/(UΔT_lm) = 7.25 m². A 1–2 shell-and-tube exchanger has ΔT = F ΔT_lm,cf with F < 1 from R = (T₁ − T₂)/(t₂ − t₁) = 1.50 and P = (t₂ − t₁)/(T₁ − t₁) = 0.333: F = 0.910, so A = 7.96 m². Keep F above about 0.75–0.8 or add shells.
Overall coefficient and fouling. For thin walls 1/U = 1/h_i + R_fi + R_fo + 1/h_o: with h_i = 2000, h_o = 1000 W/m²K the clean U = 667; fouling factors 2×10⁻⁴ m²K/W each give U = 526 W/m²K, so the area must be 1.27 times larger. The controlling (lower) coefficient dominates: raising h_i alone from 2000 to 4000 barely helps. ε–NTU method (when outlet temperatures are unknown): NTU = UA/C_min, C_r = C_min/C_max, and for counter-flow ε = [1 − e^(−NTU(1 − C_r))]/[1 − C_re^(−NTU(1 − C_r))]. With oil C = 4200 W/K and water (3 kg/s) C = 12 540 W/K, UA = 500 × 7.25 = 3625 W/K gives NTU = 0.863, C_r = 0.335 and ε = 0.538; for C_r = 0 (condenser or boiler) ε = 1 − e^(−NTU). Tube-side fluid is the fouling, corrosive or high-pressure one; baffles raise the shell-side coefficient at the cost of pressure drop.
| Quantity | Value |
|---|---|
| Duty Q, 2 kg/s oil cooled 60 K | 252 kW |
| LMTD counter-current / co-current | 69.52 K / 55.81 K |
| Area, counter-flow double-pipe | 7.25 m² |
| 1–2 shell-and-tube: F and area | 0.910; 7.96 m² |
| U clean / fouled | 667 / 526 W/m²K |
| Effectiveness, NTU = 0.863 | 0.538 |
- ΔT₁ = 80, ΔT₂ = 60
- ΔT_lm = 69.52 K
- Less area; temperatures can cross
- ΔT₁ = 120, ΔT₂ = 20
- ΔT_lm = 55.81 K
- Much smaller driving force
The design equation is Q = UAΔT_lm with ΔT_lm = (ΔT₁ − ΔT₂)/ln(ΔT₁/ΔT₂). Example: hot oil (2 kg/s, c_p = 2100 J/kg·K) cooled from 150 °C to 90 °C against water heated from 30 °C to 70 °C: Q…
Key takeaways
- Series resistances: wall L/kA, film 1/hA, cylinder ln(r₂/r₁)/2πkL; critical radius k/h; lumped analysis needs Bi < 0.1 with τ = ρc_pL_c/h.
- Semi-infinite solid: (T − T_s)/(T_i − T_s) = erf(x/2√αt); pin fin efficiency tanh(mL)/mL with m = √(4h/kd).
- Dittus–Boelter Nu = 0.023Re^0.8Pr^0.4 for turbulent heating; laminar tube Nu = 3.66 or 4.36; radiation between grey plates uses 1/ε₁ + 1/ε₂ − 1, and a shield doubles the surface resistances.
- Film condensation h ∝ (L ΔT)^(−1/4); boiling is operated below the critical flux; single-effect economy ≈ 1 and N effects ≈ N, at roughly N times the area.
- Q = UAΔT_lm (F ΔT_lm for shell-and-tube); counter-current beats co-current; add fouling resistances to 1/U; ε–NTU when outlet temperatures are unknown.
Practice questions (24)
Attempt each one before opening the answer. Every explanation names the tempting wrong option as well as the right one, because that is where marks are lost.
A wall has an inside film h = 10, brick 0.2 m (k = 0.7), insulation 0.05 m (k = 0.04), plaster 0.01 m (k = 0.8) and an outside film h = 25 W/m²K. The overall U in W/m²K (three decimals) is:
Numerical answer — type the value.
Show answer
Answer: 0.592
ΣR = 0.1 + 0.2857 + 1.25 + 0.0125 + 0.04 = 1.6882; U = 1/ΣR = 0.592 W/m²K.The critical radius of insulation for k_ins = 0.05 W/m·K on a pipe with outside coefficient h = 10 W/m²K, in mm, is:
Numerical answer — type the value.
Show answer
Answer: 5
r_c = k_ins/h_o = 0.05/10 = 0.005 m = 5 mm; insulation thinner than this raises the loss.A 20 mm steel sphere (ρ = 7800 kg/m³, c_p = 480 J/kg·K, k = 40 W/m·K) is in a stream with h = 50 W/m²K. The lumped time constant in s (nearest integer) is:
Numerical answer — type the value.
Show answer
Answer: 250
L_c = d/6 = 3.33 mm and Bi = 0.0042 < 0.1, so lumped analysis holds; τ = ρc_pL_c/h = 7800 × 480 × 0.00333/50 = 250 s.
Show the other 21 questions
A pin fin (k = 200, h = 25 W/m²K, d = 10 mm, L = 0.1 m, insulated tip) has an efficiency tanh(mL)/mL of (three decimals):
Numerical answer — type the value.
Show answer
Answer: 0.861
m = √(4h/kd) = 7.07 m⁻¹, mL = 0.707, tanh = 0.609, η = 0.861.Water at 40 °C (ρ = 992, μ = 6.53×10⁻⁴ Pa·s, k = 0.63 W/m·K, c_p = 4179 J/kg·K) flows at 1 m/s in a 25 mm tube. Using Dittus–Boelter (heating), h in W/m²K (nearest 10) is about:
Numerical answer — type the value.
Show answer
Answer: 4800
Re = 37,979, Pr = 4.33, Nu = 0.023Re^0.8Pr^0.4 = 190.6, h = Nu k/D = 4802 W/m²K.Two large parallel grey plates (ε = 0.8 and 0.5) at 500 K and 300 K exchange radiation. The net flux in W/m² (nearest integer) is:
Numerical answer — type the value.
Show answer
Answer: 1371
q = σ(T₁⁴ − T₂⁴)/(1/0.8 + 1/0.5 − 1) = 5.67×10⁻⁸ × 5.440e+10/2.25 = 1371 W/m².A single-effect evaporator concentrates 10 000 kg/h of feed from 5% to 20% solids. The water evaporated in kg/h (nearest integer) is:
Numerical answer — type the value.
Show answer
Answer: 7500
Solids 500 kg/h are conserved; product = 500/0.20 = 2500 kg/h; evaporation = 10000 − 2500 = 7500 kg/h.Compared with one effect, a triple-effect evaporator operating between the same overall temperature limits uses:
Show answer
Answer: B — about one third of the steam and roughly three times the heating area
Each effect reuses the vapour of the previous one, so steam economy rises to about 3, but the total ΔT is shared by three effects so each has one third of the driving force and the total area is about three times larger.Hot oil is cooled from 150 °C to 90 °C while cold water is heated from 30 °C to 70 °C in a counter-current exchanger. The LMTD in K (two decimals) is:
Numerical answer — type the value.
Show answer
Answer: 69.52
ΔT₁ = 150 − 70 = 80, ΔT₂ = 90 − 30 = 60; LMTD = 20/ln(80/60) = 69.52 K.The oil of 2 kg/s (c_p = 2100 J/kg·K) is cooled by 60 K. With U = 500 W/m²K and the counter-current LMTD above, the area in m² (two decimals) is:
Numerical answer — type the value.
Show answer
Answer: 7.25
Q = 2 × 2100 × 60 = 252 kW; A = Q/(U × LMTD) = 252000/(500 × 69.52) = 7.25 m².Which statements about heat exchanger design are correct?
Show answer
Answer: A — For the same terminal temperatures, counter-current LMTD is at least as large as co-current; C — Fouling resistances lower the overall coefficient
Counter-flow gives the largest mean driving force and F ≤ 1 always; fouling adds series resistance; with C_r = 0, ε = 1 − e^(−NTU), not NTU.A slab 0.1 m thick with k = 0.5 W/m·K and area 2 m² has a conduction resistance L/(kA), in K/W (one decimal), of ____.
Numerical answer — type the value.
Show answer
Answer: 0.1
R = L/(kA) = 0.1/(0.5 × 2) = 0.1 K/W. Inverting it (10 W/K) gives the conductance; resistances, not conductances, add in series.Thermal diffusivity α = k/(ρc_p) has the SI unit
Show answer
Answer: A — m²/s
(W/m·K)/((kg/m³)(J/kg·K)) = m²/s, the same unit as kinematic viscosity, which is why Pr = ν/α is dimensionless. W/m·K is the conductivity k itself, the tempting slip.Flow in a 30 mm tube gives Nu = 100 for a fluid with k = 0.6 W/m·K. The heat transfer coefficient, in W/m²·K, is ____.
Numerical answer — type the value.
Show answer
Answer: 2000
h = Nu·k/D = 100 × 0.6/0.03 = 2000 W/m²K. Multiplying by D (1.8) inverts the definition Nu = hD/k; the conductivity used is the fluid's, not the wall's.A grey surface that is a good absorber of thermal radiation at a given temperature will, by Kirchhoff's law, also have
Show answer
Answer: D — an equally high emissivity, since ε = α
ε = α at the same temperature and wavelength: good absorbers are good emitters. The sum that equals 1 is α + ρ + τ (absorptivity, reflectivity, transmissivity), the tempting mix-up; σT⁴ applies only to a black body.An evaporator produces 3000 kg/h of vapour using 2500 kg/h of steam. Its steam economy (one decimal) is ____.
Numerical answer — type the value.
Show answer
Answer: 1.2
Economy = 3000/2500 = 1.2 kg vapour per kg steam, a value only possible with more than one effect or vapour recompression. Inverting it (0.8) gives steam consumption per kg evaporated.Water (c_p = 4.18 kJ/kg·K) at 1 kg/s is heated through 20 K. The exchanger duty, in kW (one decimal), is ____.
Numerical answer — type the value.
Show answer
Answer: 83.6
Q = ṁc_pΔT = 1 × 4.18 × 20 = 83.6 kW. Using c_p = 4180 without converting J to kJ gives 83 600, which is the same duty in watts mislabelled as kW.As fouling builds up on the tubes of a heat exchanger, the overall coefficient U
Show answer
Answer: C — decreases, because a fouling resistance is added in series
1/U = 1/h_i + R_f + 1/h_o + ..., so each fouling factor lowers U and designs carry extra area to allow for it. The deposit does not add effective heat-transfer area; it insulates.A thin metal wall separates fluids with h_i = 1000 and h_o = 500 W/m²·K. Neglecting wall resistance, U, in W/m²·K (one decimal), is ____.
Numerical answer — type the value.
Show answer
Answer: 333.3
1/U = 1/1000 + 1/500 = 0.003, so U = 333.3 W/m²K, below the smaller film coefficient. Averaging the two (750) ignores that the films are resistances in series.Two large parallel black plates are at 600 K and 300 K. The net radiative flux between them, in W/m² (nearest integer), is ____.
Numerical answer — type the value.
Show answer
Answer: 6889
q = σ(T₁⁴ − T₂⁴) = 5.67 × 10⁻⁸ × (1.296 − 0.081) × 10¹¹ = 6889 W/m². Using σ(T₁ − T₂)⁴ gives 459 W/m², raising the difference rather than each temperature to the fourth power.In Nusselt film condensation on a vertical surface, the mean coefficient h varies as L^(−1/4). Doubling the surface height multiplies h by ____ (three decimals).
Numerical answer — type the value.
Show answer
Answer: 0.841
h₂/h₁ = 2^(−1/4) = 0.841: the film thickens downward, so a taller surface has a lower average coefficient. Answering 0.500 uses an L⁻¹ law, overstating the penalty.An exchanger transfers 50 kW. The smaller heat-capacity rate is 2 kW/K, and the hot and cold inlet temperatures differ by 50 K. Its effectiveness (one decimal) is ____.
Numerical answer — type the value.
Show answer
Answer: 0.5
q_max = C_min(T_h,in − T_c,in) = 2 × 50 = 100 kW, so ε = 50/100 = 0.5. Using C_max in q_max understates the possible duty and overstates ε; only the smaller stream can reach the full temperature span.A duty of 200 kW is to be met with U = 400 W/m²·K and an LMTD of 25 K. The required area, in m², is ____.
Numerical answer — type the value.
Show answer
Answer: 20
A = Q/(U·LMTD) = 200 000/(400 × 25) = 20 m². Keeping Q in kW gives 0.02 m², a thousand-fold unit slip. Substituting the answer back into the relation confirms it.A plate 20 mm thick (k = 20 W/m·K) generates heat uniformly at 10⁶ W/m³, with both faces held at 100 °C. The maximum (mid-plane) temperature, in °C (one decimal), is ____.
Numerical answer — type the value.
Show answer
Answer: 102.5
With half-thickness L = 0.01 m, T_max = T_s + q‴L²/(2k) = 100 + 10⁶ × 10⁻⁴/40 = 102.5 °C. Using the full thickness 0.02 m as L gives 110.0 °C, four times the true rise.